Parameters
7.3 Parameters
p2140[0...n]
Hysteresis speed 2 / n_hysteresis 2
Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
See also: p2155, r2197
p2141[0...n]
Speed threshold 1 / n_thresh val 1
Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the speed threshold value for the signal "f or n comparison value reached or exceeded" (BO: r2199.1).
Dependency:
See also: p2142, r2199
p2142[0...n]
Hysteresis speed 1 / n_hysteresis 1
Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the signal "f or n / v comparison value reached or exceeded" (BO: r2199.1).
Dependency:
See also: p2141, r2199
p2144[0...n]
BI: Motor stall monitoring enable (negated) / Mot stall enab neg
Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the negated enable (0 = enable) of the motor stall monitoring.
Dependency:
See also: p2163, p2164, p2166, r2197, r2198
See also: F07900
Note
When interconnecting the enable signal with r2197.7 then the stall signal is suppressed if there is no speed setpoint -
actual value deviation.
588
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: p0505
Max:
300.00 [rpm]
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: p0505
Max:
210000.00 [rpm]
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: p0505
Max:
300.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8010
Factory setting:
90.00 [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8010
Factory setting:
5.00 [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8010
Factory setting:
2.00 [rpm]
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 8012
Factory setting:
0
SINAMICS G120XA converter