Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The fault response can only be changed for faults with the appropriate identification.
Example:
F12345 and fault response = NONE (OFF1, OFF2)
--> The fault response NONE can be changed to OFF1 or OFF2.
For value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
For value = 2 (OFF2):
Internal/external pulse inhibit.
For value = 3 (OFF3):
Braking along the OFF3 down ramp followed by a pulse inhibit.
For value = 5 (STOP2):
n_set = 0
For value = 6 (armature short-circuit, internal/DC braking):
This value can only be set for all drive data sets when p1231 = 4.
a) DC braking is not possible for synchronous motors.
b) DC braking is possible for induction motors.
p2103[0...n]

BI: 1st acknowledge faults / 1st acknowledge

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the first signal source to acknowledge faults.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
A fault acknowledgment is triggered with a 0/1 signal.
p2104[0...n]

BI: 2nd acknowledge faults / 2nd acknowledge

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the second signal source to acknowledge faults.
Note
A fault acknowledgment is triggered with a 0/1 signal.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2441, 2442,
2443, 2447, 2475, 2546, 9220,
9677, 9678
Factory setting:
722.5
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2546, 8060
Factory setting:
[0] 722.5
[1] 722.5
[2] 0
[3] 0
577