NOTICE
For bit 06:
When the overspeed is reached, this bit is set and F07901 output immediately following this. The bit is canceled again
as soon as the next pulse inhibit is present.
Note
For bit 00:
The threshold value is set in p1080 and the hysteresis in p2150.
For bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
For bit 03:
1 signal direction of rotation positive.
0 signal: direction of rotation negative.
The hysteresis is set in p2150.
For bit 04:
The threshold value is set in r1119 and the hysteresis in p2150.
For bit 05:
The threshold value is set in p1226 and the delay time in p1228.
For bit 06:
The hysteresis is set in p2162.
For bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
For bit 08:
The threshold value is set in p2170 and the delay time in p2171.
For bit 09, 10:
The threshold value is set in p2172 and the delay time in p2173.
For bit 11:
The threshold value is set in p2179 and the delay time in p2180.
For bit 13:
Only for internal Siemens use.
r2198.4...12

CO/BO: Status word monitoring 2 / ZSW monitor 2

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Display and BICO output for the second status word of the monitoring functions.
Bit field:
Bit
04
05
06
07
08
11
12
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Speed setpoint - actual value deviation in tolerance t_off
I_act >= I_threshold value p2170
Vdc_act <= Vdc_threshold value p2172
Vdc_act > Vdc_threshold value p2172
Output load is not present
|n_act| > n_max (F07901)
Signal name
|n_set| < p2161
n_set > 0
Motor blocked
Motor stalled
|I_act| < I_threshold value p2170
Load in the alarm range
Load in the fault range
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
7.3 Parameters
No
8011
No
8022
No
8022
No
8022
No
8022
No
-
Data type: Unsigned16
Dynamic index: -
Function diagram: 2536
Factory setting:
-
0 signal
FP
No
8011
No
8011
No
8012
No
8012
No
8022
No
8013
No
8013
601