Ramp-Down Time For The Off3 Command; Complete Quick Commissioning - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Figure 5-11

Ramp-down time for the OFF3 command

Motor data identification: Select the method which the converter uses to measure the data of
the connected motor:
● OFF: Motor data is not measured.
● STIL ROT: Recommended setting: Measure the motor data at standstill and with the motor
rotating. The converter switches off the motor after the motor data identification has been
completed.
● STILL: Measure the motor data at standstill. The converter switches off the motor after the
motor data identification has been completed.
Select this setting if one of the following cases is applicable:
– You have selected control mode "SPD N EN", but the motor cannot rotate freely.
– You have selected U/f control as control mode, e.g. "VF LIN" or "VF QUAD".
● ROT: Measure the motor data while the motor is rotating. The converter switches off the
motor after the motor data identification has been completed.
● ST RT OP: setting same as STIL ROT.
After the motor data identification, the motor accelerates to the current setpoint.
● STILL OP: setting same as STILL.
After the motor data identification, the motor accelerates to the current setpoint.

Complete quick commissioning:

Switchover the display using an arrow key: nO → YES
Press the OK key.
You have completed quick commissioning.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
5.4 Quick commissioning using the BOP-2 operator panel
Ramp-up and ramp-down time of the motor
Commissioning
121