p1580[0...n]
Efficiency optimization / Efficiency opt.
CUG120XA_USS
Access level: 3
(PM330)
Can be changed: T, U
Unit group: -
Min:
0 [%]
Description:
Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Dependency:
See also: p0500
Note
It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
p1581[0...n]

Flux reduction factor / Flux red factor

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [%]
Description:
The following applies for a synchronous reluctance motor:
Sets the lower limit of the flux setpoint to evaluate the optimum flux characteristic.
The value is referred to the rated motor flux (p0357 * r0331).
p1582[0...n]

Flux setpoint smoothing time / Flux setp T_smth

Access level: 3
Can be changed: T, U
Unit group: -
Min:
4 [ms]
Description:
Sets the smoothing time for the flux setpoint.
p1596[0...n]

Field weakening controller integral-action time / Field_ctrl Tn

Access level: 3
Can be changed: T, U
Unit group: -
Min:
10 [ms]
Description:
Sets the integral-action time of the field-weakening controller.
r1598
CO: Total flux setpoint / Flux setp total
Access level: 3
Can be changed: -
Unit group: -
Min:
- [%]
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: -
Max:
100 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
100 [%]
Calculated: CALC_MOD_REG Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
5000 [ms]
Calculated: CALC_MOD_CON Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
10000 [ms]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 6722
Factory setting:
100 [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
100 [%]
Dynamic index: DDS, p0180
Function diagram: 6722, 6724
Factory setting:
15 [ms]
Dynamic index: DDS, p0180
Function diagram: 6723, 6724
Factory setting:
300 [ms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6714, 6723,
6724, 6725, 6726
Factory setting:
- [%]
531