Co: Technology Controller Fixed Value 15 / Tec_Ctr Fix Val 15; Technology Controller Fixed Value Selection Method; Bi: Technology Controller Fixed Value Selection Bit 0; Bi: Technology Controller Fixed Value Selection Bit 1 - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p2215[0...n]

CO: Technology controller fixed value 15 / Tec_ctr fix val 15

Access level: 2
Can be changed: T, U
Unit group: 9_1
Min:
-200.00 [%]
Description:
Sets the value for fixed value 15 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2216[0...n]
Technology controller fixed value selection method / Tec_ctr FixVal sel
Access level: 2
Can be changed: T
Unit group: -
Min:
1
Description:
Sets the method to select the fixed setpoints.
Value:
1:
2:
p2220[0...n]
BI: Technology controller fixed value selection bit 0 / Tec_ctrl sel bit 0
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2221, p2222, p2223
p2221[0...n]
BI: Technology controller fixed value selection bit 1 / Tec_ctrl sel bit 1
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2220, p2222, p2223
p2222[0...n]
BI: Technology controller fixed value selection bit 2 / Tec_ctrl sel bit 2
Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2220, p2221, p2223
606
Direct selection
Binary selection
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
2
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 7950
Factory setting:
150.00 [%]
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: 7950, 7951
Factory setting:
1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 7950, 7951
Factory setting:
0
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 7950, 7951
Factory setting:
0
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 7950, 7951
Factory setting:
0
SINAMICS G120XA converter

Advertisement

Table of Contents
loading

Table of Contents