Acx: Parameter Back-Up File Missing; Acx: Loading The Parameter Back-Up File Unsuccessful - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Cause:
When the Control Unit is booted, no complete data set was found from the parameter back-up files. The last time that the
parameterization was saved, it was not completely carried out.
It is possible that the backup was interrupted by switching off or withdrawing the memory card.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = 01 hex:
Power up was realized without data backup. The drive is in the factory setting.
aa = 02 hex:
The last available internal backup data record was loaded. The parameterization must be checked. It is recommended that
the parameterization is downloaded again.
aa = 03 hex:
The last available data record from the memory card was loaded. The parameterization must be checked.
aa = 04 hex:
An invalid data backup was loaded from the memory card into the drive. The drive is in the factory setting.
dd, cc, bb:
Only for internal Siemens troubleshooting.
See also: p0971 (Save parameters)
Remedy:
- Download the project again with the commissioning software.
- save all parameters (p0971 = 1 or "copy RAM to ROM").
See also: p0971 (Save parameters)
F01036 (A)

ACX: Parameter back-up file missing

Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When downloading the device parameterization, a parameter back-up file PSxxxyyy.ACX associated with a drive object
cannot be found.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file name PSxxxyyy.ACX
yyy = 000 --> consistency back-up file
yyy = 001 ... 062 --> drive object number
yyy = 099 --> PROFIBUS parameter back-up file
Byte 2, 3, 4:
Only for internal Siemens troubleshooting.
Remedy:
If you have saved the project data using the commissioning software, carry out a new download for your project.
Save using the function "Copy RAM to ROM" or with p0971 = 1.
This means that the parameter files are again completely written into the non-volatile memory.
Note:
If the project data have not been backed up, then a new first commissioning is required.
F01038 (A)

ACX: Loading the parameter back-up file unsuccessful

Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
759