Advanced commissioning
6.2 Drive control
Example
To output converter fault messages via digital output DO 1, you must interconnect DO 1 with
these fault messages.
Set p0731 = 52.3
Parameters
Table 6-3
Parameter
r0052[0...15]
r0053[0...11]
You can find additional binector outputs in the parameter list.
See also
Interconnecting signals in the converter (Page 882)
138

Frequently used binector outputs (BO) of the converter

Description
CO/BO: Status word 1
.00
1 signal: Ready for switching on
.01
1 signal: Ready for operation
.02
1 signal: Operation enabled
.03
1 signal: Fault active: The converter inverts signal
r0052.03 if it is interconnected to a digital output.
.04
0 signal: OFF2 active
.05
0 signal: OFF3 active
.06
1 signal: Switching on inhibited active
.07
1 signal: Alarm active
.08
0 signal: Deviation, setpoint/actual speed
.09
1 signal: Control request
.10
1 signal: Maximum speed (p1082) reached
.11
0 signal: I, M, P limit reached
.13
0 signal: Alarm, motor overtemperature
.14
1 signal: Motor clockwise rotation
.15
0 signal: Alarm, converter overload
CO/BO: Status word 2
.00
1 signal: DC braking active
.02
1 signal: Speed > minimum speed (p1080)
.06
1 signal: Speed ≥ setpoint speed (r1119)
Parameters (Page 352)
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB