PROFIsafe: cycle time %1 [ms] too long
%1 = Parameterized cycle time
The PROFIsafe communication cycle time resulting from MD
$MN_PROFISAFE_IPO_TIME_RATIO and MD $MN_IPO_CYCLE_TIME exceeds the
permissible limit value (25 ms).
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Adapt cycle time via MD $MN_PROFISAFE_IPO_TIME_RATIO or correct the reduction
of the IPO cycle.
Switch control OFF - ON.
PROFIsafe: MD %1[%2]: bus segment %3 error
%1 = MD name
%2 = MD array index
%3 = Parameterized bus segment
An incorrect bus segment was entered in the specified machine data. The value must be
5.
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Correct the MD.
Switch control OFF - ON.
PROFIsafe: MD %1[%2]: address %3 error
%1 = MD name
%2 = MD array index
%3 = Parameterized PROFIsafe address
An incorrect PROFIsafe address was entered in the specified machine data. The value
must be greater than 0.
- Mode group not ready.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Correct the MD.
Switch control OFF - ON.