1 Alarms
Definitions:
Reactions:
Remedy:
Program Continuation:
14011
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
14012
Parameters:
Definitions:
1-174
In a subroutine call with parameter transfer, parameters have been omitted that cannot be
replaced by default parameters (call-by-reference parameters or parameters of type
AXIS. The other missing parameters are defaulted with the value 0 or with the unit frame
in the case of frames).
- Correction block is reorganized.
- Interface signals are set.
- Alarm display.
The missing parameters must be provided with values in the subroutine call.
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 program %3 not existing or will be edited
%1 = Channel number
%2 = Block number, label
%3 = Program name
An unknown identifier (string) was found in the part program. It is therefore assumed that
this is a program name. The part program indicated in a subprogram call or SETINT state-
ment does not exist or is not released for machining.
As of SW 5, when a program is edited on the MMC, it can no longer be started with NC
Start.
This alarm occurs if the PI FB-4 is being applied to a non-existent program.
- Correction block is reorganized.
- Interface signals are set.
- Alarm display.
The alarm may have different causes:
• Typing error of the identifier stated in parameter 3
• Check subprogram call/SETINT statement or PROC statement. Reload part program
and release for machining or close MMC editor.
• The PI "_N_ASUP__" FB-4, analog to the SETINT instruction, may want to select a non-
existent program
• Wrong path definition in subprogram call when subprogram is not called up via a search
path but via an absolute path definition. Examples of complete path definitions: /
_N_directoryName_DIR/_N_programName_SPF or /_N_WKS_DIR/_N_wpdName_WPD/
_N_programName_SPF. directoryName: MPF, SPF, CUS, CMA, CST (defined directo-
ries). wpdName: user-specific identifier of workpiece directory (max. of 24 characters).
programName: name of subprogram (max. of 24 characters)
• Parameter 3 can be a macro name. The macro definition file has an inappropriate con-
tent or it is not stored in the directory DEF_DIR or it has not been set active (via POW-
ERON or via MMC operating step or by PI service 'F_COPY').
• Parameter 3 can be a GUD variable. There is no GUD definition file defining the variable
or it is not stored in the directory DEF_DIR or it has not been set active (via the
INITIAL_INI procedure or via MMC operating step or by PI service 'F_COPY').
• The part program could also be started from the CPU (ASUP).
• Note: It could also be a program started by PLC PROG_EVENT_DESK.
Clear alarm with NC START or RESET key and continue the program.
Channel %1 block %2 maximum subroutine level exceeded
%1 = Channel number
%2 = Block number, label
The maximum nesting depth of 8 program levels has been exceeded.
Subroutines can be called from the main program, and these in turn may have a nesting
depth of 7.
In interrupt routines the maximum number of levels is 4!