1 Alarms
15030
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
15100
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
15110
Parameters:
Definitions:
Reactions:
1-236
Channel %1 block %2 different measurement system settings
%1 = Channel number
%2 = Block number, label
The INCH or METRIC instruction describes the system of measurement in which the data
blocks have been read from the control. In order to prevent the incorrect interpretation of
data intended for a particular system of measurement, a data block is only accepted if the
above instruction matches the active system of measurement.
- Interpreter stop
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
Change the system of measurement or load a data block which matches the system of
measurement.
Clear alarm with the RESET key. Restart part program.
Channel %1 block %2 REORG abort caused by log file overflow
%1 = Channel number
%2 = Block number, label
In order to synchronize the preprocessing run and the main run with REORG, the control
accesses modification data which are maintained in a logfile. The alarm indicates that no
more capacity is available in the logfile for the specified block in the channel.
- Interpreter stop
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
Please inform the authorized personnel/service department. No remedial measures are
available for the further execution of the current NC program, however:
1. Reduce log file size requirement by:
Reducing the distance between the preprocessing and the main run via appropriate pre-
processing stops STOPRE.
2. The logfile should be increased in size by means of the channel-specific data:
Modify MD 28000: MM_REORG_LOG_FILE_MEM and
Modify MD 28010: MM_REORG_LUD_MODULES
Attention!
A change in these machine data also causes a reallocation of the NCK user memory and
the standard machine data are then loaded. Unless a data save is performed, there will be
a LOSS OF DATA!'
Clear alarm with the RESET key. Restart part program.
Channel %1 block %2 REORG not possible
%1 = Channel number
%2 = Block number, label
In order to synchronize the preprocessing run and the main run with REORG, the control
accesses modification data which are maintained in a logfile. The alarm indicates that no
more capacity is available in the logfile for the specified block in the channel.
The alarm message means that the logfile has been deleted in order to obtain additional
memory for program reorganization. Consequently, it is no longer possible to REORG the
preprocessing memory up to the next coincidence point.
- Alarm display.
 Siemens AG, 2004. All rights reserved
SINUMERIK 840D/840Di/810D Diagnostics Guide (DA), 10.04 Edition