Omron Q2A Series Technical Manual page 826

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.11 T: AUTOTUNING
T1-07 Motor Base Speed
No.
Name
(Hex.)
T1-07
Motor Base Speed
(0707)
T1-08 PG PulsePerRevolution
No.
Name
(Hex.)
T1-08
PG PulsePerRevolution
(0708)
Set the actual number of pulses for one full motor rotation.
T1-09 Motor NoLoad Current
No.
Name
(Hex.)
T1-09
Motor NoLoad Current
(0709)
Note:
The display units are different for different models:
• 4002 to 4023: 0.01 A
• 4031 to 4675: 0.1 A
The value shown is the no-load current that is automatically calculated from the values set in T1-02 [Motor Rated
Power] and T1-04 [Motor Rated Current]. Set the no-load current shown on the motor test report. If the motor
test report is not available, do not change this parameter.
T1-10 Motor Rated Slip Frequency
No.
Name
(Hex.)
T1-10
Motor Rated Slip
Frequency
(070A)
Shows 0.000 Hz as the default value. Set the rated slip shown on the motor test report. If the motor test report is
not available, do not change this parameter.
T1-11 Motor Iron Loss
No.
Name
(Hex.)
T1-11
Motor Iron Loss
(070B)
Note:
The default setting is different for different motor codes and motor parameter settings.
The value shown is the E2-10 [Motor Iron Loss] or E4-10 [M2 Iron Loss] for the motor output set in T1-02
[Motor Rated Power]. If the motor test report is available, enter the motor iron loss value to T1-11.
T1-12 Test Mode Selection
No.
Name
(Hex.)
T1-12
Test Mode Selection
(0BDB)
0 : No
1 : Yes
After Auto-Tuning, the drive automatically sets E2-02 [Mot Rated Slip] and E2-03 [Mot No-Load Current] when
you operate the motor for the first time in Drive Mode.
826
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor base speed for Auto-Tuning (min
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of PG (pulse generator, encoder) pulses.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the no-load current of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated slip.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the iron loss for calculating the energy-saving coefficient.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable Test Mode after Stationary Auto-Tuning. When you can operate the
motor with a light load attached after Stationary Auto-Tuning is complete, enable this parameter.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
-1
(r/min)).
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
-1
1450 min
(r/min)
-1
(0 - 35400 min
(r/min))
Default
(Range)
1024 ppr
(0 - 60,000 ppr)
Default
(Range)
-
(0A - T1-04; max. of
2999.9)
Default
(Range)
-
(0.000 - 20.000 Hz)
Default
(Range)
Determined by E2-11 or
E4-11
(0 - 65535 W)
Default
(Range)
0
(0, 1)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents