11.9 L: PROTECTION

11.9

L: PROTECTION

L1: MOTOR PROTECTION

No.
Name
(Hex.)
L1-01
Motor Cool Type for
OL1 Calc
(0480)
L1-02
OL1 Protect Time
(0481)
L1-03
Motor oH AL Reaction
Select
(0482)
L1-04
Motor oH FLT Reaction
Select
(0483)
L1-05
Motor Therm.Filter Time
(0484)
L1-08
oL1 Current Level
(1103)
L1-09
M2 oL1 Curr.Level
(1104)
L1-13
Motor oL1 Memory
Selection
(046D)

L2: POWER LOSS RIDE THROUGH

No.
Name
(Hex.)
L2-01
RideThru@PwrLoss
(0485)
L2-50
RidThruMode@PwrLoss
(0453)
448
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor overload protection with electronic thermal protectors.
0 : Disabled
1 : VTorque
2 : CT 10:1 Speed Range
3 : CT 100:1 SpeedRange
4 : PM VTorque
5 : PM CTorque
6 : VT (50Hz)
Note:
When only one motor is connected to a drive, set L1-01 = 1 to 6 [Enabled].
External thermal relays are not necessary in these conditions.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the operation time for the electronic thermal protector of the drive to prevent
damage to the motor. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets drive operation when the PTC input signal entered into the drive is at the oH3
[Motor Overheat Alarm] detection level.
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation when the PTC input signal to the drive is at the oH4 [Motor
Overheat Fault (PTC Input)] detection level.
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant for the PTC input signal entered to the drive. This
parameter prevents accidental motor overheat faults.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the reference current for the motor 1 thermal overload detection.
Note:
When the current level > 0.0 A, you cannot set this value < 10% of drive rated
current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the reference current for the motor 2 thermal overload detection.
Note:
When the current level > 0.0 A, you cannot set this value < 10% of drive rated
current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that keeps the current electronic thermal protector value when the
drive stops receiving power.
0 : Disabled
1 : Enabled
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation after a momentary power loss.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive operation after a momentary power loss..
0 : Timer Controlled
1 : While CPU Active
2 : KEB Mode
3 : KEB Stop Mode
4 : KEB Decel to Stop
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
Ref.
(Range)
Determined by A1-02
202
(0 - 6)
1.0 min
204
(0.1 - 5.0 min)
3
205
(0 - 3)
1
205
(0 - 2)
0.20 s
742
(0.00 - 10.00 s)
0.0 A
742
(0.0 A or 10% to 150%
of the drive rated
current)
0.0 A
742
(0.0 A or 10 to 150% of
the drive rated current)
1
743
(0, 1)
Default
Ref.
(Range)
0
748
(0, 1)
0
752
(0 - 4)