Omron Q2A Series Technical Manual page 757

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

Figure 12.131 Stall Prevention Level during Run with Analog Input
L3-11 Overvolt Supression Select
No.
Name
(Hex.)
L3-11
Overvolt Supression Select
(04C7)
0 : Disabled
The drive does not adjust the regenerative torque limit or the output frequency. If you apply a regenerative load,
the drive can detect an ov [Overvoltage] fault. Use this setting with a dynamic braking option.
1 : Enabled
When a regenerative load increases the DC bus voltage, the drive decreases the regenerative torque limit and
increases the output frequency to prevent ov
L3-17 DCBus Regul.Level
No.
Name
(Hex.)
L3-17
DCBus Regul.Level
(0462)
Note:
This value is initialized when E1-01 [Input AC Supply Voltage] is changed.
Sets this parameter for any of the following circumstances.
• L3-11 = 1 [Overvolt Supression Select = Enabled].
• L3-04 = 1 [StallP@Decel Enable = Enabled] and L3-50 = 1 [StallP@Decel Mode = Automatic Decel
Reduction].
L3-20 DCBus VoltAdj Gain
No.
Name
(Hex.)
L3-20
DCBus VoltAdj Gain
(0465)
Expert
Set one of these parameters to enable L3-20:
• L2-29 = 2 [KEB Method = Single KEB2 Ride-Thru]
• L3-04 = 1 [StallP@Decel Enable = Enabled] and L3-50 = 1 [StallP@Decel Mode = Automatic Decel
Reduction]
• L3-11 = 1 [Overvolt Supression Select = Enabled]
• H1-xx = 42 or 43 [DI Function Select = KEB Thru2 NC or KEB Thru2 NO]
Note:
• If stall prevention during deceleration function causes ov [Overvoltage] and Uv1 [DC Bus Undervoltage] faults when you start
deceleration and L2-29 = 1, H1-xx = 42 or 43, or L3-04 = 2, gradually increase this parameter in 0.1-unit increments. If the setting
value is too high, it can cause large speed or current ripples.
• If sudden increases in the regenerative load cause ov faults and L3-11 = 1, gradually increase this parameter in 0.1-unit increments. If
the setting value is too high, it can cause large speed or current ripples.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the overvoltage suppression function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the target value for the DC bus voltage when the overvoltage suppression function and the
Decel Stall Prevention function (Intelligent Stall Prevention) are active.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the proportional gain used to control the DC bus voltage.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 L: PROTECTION
Default
(Range)
0
(0, 1)
Default
(Range)
400 V Class: 750 V
(400 V Class: 300 - 800 V)
Default
(Range)
Determined by A1-02
(0.00 - 5.00)
757
12