Omron Q2A Series Technical Manual page 653

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

Note:
• The setting range changes if using MECHATROLINK-II or MECHATROLINK-III:
–MECHATROLINK-II (SI-T3) range: 20 to 3F
–MECHATROLINK-III (SI-ET3) range: 03 to EF
• Be sure to set a node address that is different than all other node addresses. Incorrect parameter settings will cause AEr [Station
Address Setting Error] errors and the L.ERR LED on the option will come on.
• The drive detects AEr errors when the station address is 20 or 3F.
F6-21 MLII Frame Size
No.
Name
(Hex.)
F6-21
MLII Frame Size
(036C)
0 : 32-byte
1 : 17-byte
F6-22 MLII Link Speed
No.
Name
(Hex.)
F6-22
MLII Link Speed
(036D)
Note:
This parameter is only available with the MECHATROLINK-II option.
0 : 10 Mbps
1 : 4 Mbps
F6-23 MLII Mon Sel (E)
No.
Name
(Hex.)
F6-23
MLII Mon Sel (E)
(036E)
To enable the Modbus register set in F6-23, set SEL_MON2/1 to 0EH or set SEL_MON 3/4 and SEL_MON 5/6
to 0EH. Bytes of the response data enable the Modbus register content that was set in F6-23.
F6-24 MLII Mon Sel (F)
No.
Name
(Hex.)
F6-24
MLII Mon Sel (F)
(036F)
To enable the Modbus register set in F6-24, set SEL_MON2/1 to 0FH or set SEL_MON3/4 and SEL_MON 5/6 to
0FH. Bytes of the response data enable the Modbus register content that was set F6-24.
F6-25 MLII Watchdog Error Sel
No.
Name
(Hex.)
F6-25
MLII Watchdog Error Sel
(03C9)
0 : Ramp->Stop
The drive ramps to stop in the set deceleration time. Fault relay output terminal 1NO-1CM will activate, and
1NC-1CM will deactivate.
1 : Coast->Stop
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frame size for MECHATROLINK communication. Restart the drive after you change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the communications speed for MECHATROLINK-II. Restart the drive after you change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Modbus register used for the monitor functions of INV_CTL (drive operation control
command) and INV_I/O (drive I/O control command). Restart the drive after you change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Modbus register used for the monitor functions of INV_CTL (drive operation control
command) and INV_I/O (drive I/O control command). Restart the drive after you change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor or let the motor continue operating when the drive detects an E5
[MECHATROLINK Watchdog Timer Err].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.6 F: OPTIONS
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0000h
(0000h - FFFFh)
Default
(Range)
0000h
(0000h - FFFFh)
Default
(Range)
1
(0 - 3)
12
653