Omron Q2A Series Technical Manual page 760

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.8 L: PROTECTION
L3-27 StallP Detect Time
No.
Name
(Hex.)
L3-27
StallP Detect Time
(0456)
L3-34 Torque Lim.Delay Time
No.
Name
(Hex.)
L3-34
Torque Lim.Delay Time
(016F)
Expert
When vibration occurs during operation of Single Drive KEB Ride-Thru 2, increase this parameter in 0.010-unit
increments.
Note:
The Single Drive KEB Ride-Thru 2 mode operates when L2-29 = 2 [KEB Method = Single KEB2 Ride-Thru] and H1-xx = 42 or 43 [DI
Function Selection = KEB Thru2 NC or KEB Thru2 NO].
L3-35 SpAgree Width@StallP
No.
Name
(Hex.)
L3-35
SpAgree Width@StallP
(0747)
Expert
Set this parameter when hunting occurs while you use a frequency reference through an analog input.
L3-36 VibSup Gain@Accel
No.
Name
(Hex.)
L3-36
VibSup Gain@Accel
(11D0)
If there is vibration in the output current during acceleration, increase the setting value.
Note:
Set L3-01 = 4 [StallP Mode@Accel = ILim Mode] to enable this function.
L3-37 CurLim ITime@Accel
No.
Name
(Hex.)
L3-37
CurLim ITime@Accel
(11D1)
Expert
Note:
Set L3-01 = 3 [StallP Mode@Accel = Intelligent Accel] to enable this function.
L3-38 CurLim PGain@Accel
No.
Name
(Hex.)
L3-38
CurLim PGain@Accel
(11D2)
Expert
Note:
Set L3-01 = 4 [StallP Mode@Accel = ILim Mode] to enable this function.
760
V/f
CL-V/f
OLV
CLV
AOLV
Sets a delay time between reaching the Stall Prevention level and starting the Stall Prevention
function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the filter time constant that returns the torque limit to its initial value when KEB operation
operates in Single Drive KEB Ride-Thru mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width for speed agreement when L3-04 = 1 [StallP@Decel Enable = Enabled] and L3-50
= 1 [StallP@Decel Mode = Automatic Decel Reduction]. Usually it is not necessary to change
this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to suppress current and motor speed hunting during operation when L3-01 = 4
[StallP Mode@Accel = ILim Mode]. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Suppresses current hunting and overshooting that occurs when the drive stalls during acceleration.
Usually it is not necessary to change this setting.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
50 ms
(0 - 5000 ms)
Default
(Range)
Determined by A1-02
(0.000 - 1.000 s)
Default
(Range)
0.00 Hz
(0.00 - 1.00 Hz)
Default
(Range)
Determined by A1-02
(0.0 - 100.0)
Default
(Range)
5 ms
(0 - 100 ms)
Default
(Range)
10.0
(0.0 - 100.0)

Hide quick links: