12.7 H: TERMINALS
Calibrate Terminal AO1
Stop the drive to calibrate meters. Use this procedure to calibrate:
1. Show H4-02 [AO1 An.Out Gain] on the keypad.
Terminal AO1 outputs the analog signal when the monitor item that you set in H4-01 [AO1 An.Out Select] is
100%.
2. Adjust H4-02 and monitor the meter scale connected to terminal AO1.
3. Show H4-03 [AO1 An.Out Bias] on the keypad.
The analog signal at the time when the monitor item selected with H4-01 is 0% is output from terminal AO1.
4. Adjust H4-03 while referencing the meter scale connected to terminal AO1.
Calibrate Terminal AO2
Stop the drive to calibrate meters. Use this procedure to calibrate:
1. Show H4-05 [AO2 An.Out Gain] on the keypad.
Terminal AO2 outputs the analog signal when the monitor item that you set in H4-04 [AO2 An.Out Select] is
100%.
2. Adjust H4-05 and monitor the meter scale connected to terminal AO2.
3. Show H4-06 [AO2 An.Out Bias] on the keypad.
Terminal AO2 outputs the analog signal when the monitor item that you set in H4-04 [AO2 An.Out Select] is
0%.
4. Adjust H4-03 and monitor the meter scale connected to terminal AO1.
H4-01 AO1 An.Out Select
No.
Name
(Hex.)
H4-01
AO1 An.Out Select
(041D)
Set the x-xx part of the U: MONITORS. For example, set H4-01 to 102 to monitor U1-02 [Output Frequency].
Note:
• The configurable monitor changes when the control method changes.
• To use in through mode, set this parameter to 000 or 031. You can set the terminal AO1 output level from the PLC through Modbus
communications or the communication option.
H4-02 AO1 An.Out Gain
No.
Name
(Hex.)
H4-02
AO1 An.Out Gain
(041E)
RUN
The analog signal output from the AO1 terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-07 [AO1 Signal Level Select].
724
Figure 12.108 Analog Output Gain/Bias Configuration Example 2
V/f
CL-V/f
OLV
Sets the monitor number to send from MFAO terminal AO1.
V/f
CL-V/f
OLV
Sets the gain of the monitor signal that is sent from MFAO terminal AO1.
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
(-999.9 - +999.9%)
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
102
(000 - 999)
Default
(Range)
100.0%