B: Application; B1: Operation Mode Select - Omron Q2A Series Technical Manual

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.2

b: APPLICATION

The parameter group b: APPLICATION sets the following functions.
• Frequency reference source/Run command source
• Stopping method settings
• DC Injection Braking
• Speed Search
• Timer Function
• PID control
• Dwell function
• Droop control
• Energy Savings Control
• Zero Servo Control

b1: OPERATION MODE SELECT

b1 parameters set the operation mode for the drive.
b1-01 Freq. Ref. Sel. 1
No.
Name
(Hex.)
b1-01
Freq. Ref. Sel. 1
(0180)
Note:
• Push
on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
• When the drive receives a Run command when the frequency reference is 0 Hz or less than the E1-09 [Min Output Frequency] value,
on the keypad will flash. Check the setting for the frequency reference input and enter a value more than or equal to the E1-09
value.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals AI1, AI2, and AI3 to input an analog frequency reference with a voltage or current input
signal.
• Voltage Input
Refer to
Table 12.3
to use a voltage signal input to one of the MFAI terminals.
Terminal Signal
Terminal
Level
AI1
0 - 10 V
-10 - 10 V
AI2
0 - 10 V
-10 - 10 V
AI3
0 - 10 V
-10 - 10 V
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for the frequency reference.
Table 12.3 Frequency Reference Voltage Input
Parameter Settings
Signal Level
Function Selection
Selection
H3-01 = 0
H3-02 = 0
[Frequency Reference]
H3-01 = 1
H3-09 = 0
H3-10 = 0
[Frequency Reference]
H3-09 = 1
H3-05 = 0
H3-06 = 0
[Frequency Reference]
H3-05 = 1
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Gain
Bias
H3-03
H3-04
H3-11
H3-12
H3-07
H3-08

12.2 b: APPLICATION

Default
(Range)
1
(0 - 4)
Note
Set DIP switch S1-1 to "V" for
voltage input.
Set DIP switch S1-2 to "V" for
voltage input.
Set DIP switch S1-3 to "V" for
voltage input.
Set DIP switch S4 to "AI" for
analog input.
515
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents