L9: Drive Protection 2 - Omron Q2A Series Technical Manual

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

11.9 L: PROTECTION
No.
Name
(Hex.)
L8-40
Carrier Red Off-Delay
Time
(04F1)
L8-41
HCA alarm Selection
(04F2)
L8-51
STPo Current Level
(0471)
Expert
L8-52
STPo Integral Level
(0472)
Expert
L8-53
STPo Integral Time
(0473)
Expert
L8-54
STPo Id Diff Detection
(0474)
Expert
L8-55
DB IGBT Protection
(045F)
L8-56
StallP@Acc Activation
Time
(047D)
Expert
L8-57
StallP Retry Counts
(047E)
Expert
L8-90
STPo Detect Level
(0175)
Expert
L8-93
Lso Detect Time
(073C)
Expert
L8-94
Lso Detect Level
(073D)
Expert
L8-95
Lso Amount
(077F)
Expert

L9: DRIVE PROTECTION 2

No.
Name
(Hex.)
L9-16
FAn1 Detect Time
(11DC)
Expert
456
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time until the automatically reduced carrier frequency returns to the
condition before the reduction.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to cause an HCA [Current Alarm] when the output current is more
than 150% of the drive rated current.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the STPo [Desynchronization Error] detection level as a percentage of the output
current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for STPo [Desynchronization Error] related to the ACR integral
value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time until the drive detects STPo after exceeding the value of L8-51
[STPo Current Level].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Id deviation detection function for STPo [Desynchronization Error].
0 : Disable
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the protection function for the internal braking transistor.
0 : Disable
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length time that the acceleration stall prevention function can continue to
operate before the drive detects an STPo [Desynchronization Error].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of times the acceleration stall prevention function can operate until
speeds match before the drive detects an STPo [Desynchronization Error].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level that the control fault must be equal to or more than to cause an
STPo [Desynchronization Error].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time the drive will wait to start baseblock after detecting LSo [LSo
Fault].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for LSo [Low Speed Motor Step-Out] as a percentage of E1-04
[Max Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the average count of LSo [Low Speed Motor Step-Out] detections.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for FAn1 [Drive Cooling Fan Failure]. The manufacturer
recommends that you do not change this parameter value.
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
Ref.
(Range)
Determined by A1-02
780
(0.00 - 2.00 s)
0
780
(0, 1)
0.0%
780
(0.0 - 300.0%)
1.0
780
(0.1 - 2.0)
1.0 s
780
(1.0 - 10.0 s)
1
780
(0, 1)
1
781
(0, 1)
5000 ms
781
(100 - 5000 ms)
10 times
781
(1 - 10 times)
Determined by A1-02
781
(0 - 5000 times)
1.0 s
781
(0.0 - 10.0 s)
3%
782
(0 - 10%)
10 times
782
(1 - 50 times)
Default
Ref.
(Range)
4.0 s
782
(0.0 - 30.0 s)