After Stationary Auto-Tuning is complete, use this procedures to do the operation in test mode:
1. Check the E2-02 and E2-03 values on the "Modified Parameters/Fault Log" screen or the "Parameters" screen.
2. Operate the motor in Drive Mode with these conditions:
• Do not disconnect the wiring between the motor and drive.
• Do not lock the motor shaft with a mechanical brake or other device.
• The maximum motor load must be 30% of the rated load.
• Keep a constant speed of 30% of E1-06 [Base Frequency] (default value = maximum frequency) or more
for 1 second or longer.
3. After the motor stops, check the E2-02 and E2-03 values on the "Modified Parameters/Fault Log" screen or
the "Parameters" screen again.
4. Make sure that the input data is correct.
When the settings in E2-02 and E2-03 are different than in step 1, the drive set the values automatically.
Note:
• If you cannot operate the motor with the conditions in step 2 for the first test run and if the values set in E2-02 and E2-03 are much
different than data in the official test report for the motor and the data listed in
page
489, these problems can occur:
–Motor vibrations or hunting
–Not sufficient torque
–Overcurrent
In elevator applications, there is a risk of the cage falling and causing personal injury.
Do one of these precautions to decrease the risk:
–After doing Stationary Auto-Tuning, operate the drive as specified by the conditions and procedure above.
–Set T1-12 = 0 [Test Mode Selection = No].
–Do Rotational Auto-Tuning.
• If you initialize the drive after completing Step 1, do the procedure beginning from Step 1 again.
• For general-purpose motors, the target value for E2-02 is 1 Hz to 3 Hz, and the target rated current for E2-03 is 30% to 65%. Larger
capacity motors have a lower rated slip, and a smaller ratio for the no-load current rated current. Refer to
Duty Rating ND/HD on page 489
Precautions before Stationary Auto-Tuning for Line-to-Line Resistance and Stator
Resistance Auto-Tuning
In V/f control, when the motor cable is 50 meters (164 feet), do Stationary Auto-Tuning for Line-to-Line
Resistance.
WARNING! Electrical Shock Hazard. In Stationary Auto-Tuning, the drive applies voltage to the motor. Do not touch the motor
until Auto-Tuning is complete. Failure to obey could cause serious injury.
Precautions before Inertia Tuning and ASR Tuning
Before Inertia Tuning or ASR Tuning, check these items:
WARNING! Electrical Shock Hazard. In Rotational Auto-Tuning, the drive applies voltage to the motor before the motor rotates.
Do not touch the motor until Auto-Tuning is complete. Failure to obey could cause serious injury.
• Do rotational motor parameter tuning or look at the motor test report or nameplate to enter the values manually.
• Make sure that the motor magnetic brake is released.
• Connect the motor and load.
• Make sure that external force from the machine will not cause the motor to rotate.
• Make sure that the machine does not prevent reverse rotation. You cannot do Inertia Tuning or ASR Tuning with
machines that prevent reverse rotation.
• When the motor can rotate during Auto-Tuning, check for safety issues near the drive, motor, and machine.
Note:
If there are gears between the machine and motor shaft, Inertia Tuning or ASR Tuning are possibly not applicable.
Precautions before Using Deceleration Rate Tuning and KEB Tuning
Before Deceleration Rate Tuning or KEB Tuning, check these items:
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
for details.
Defaults by Drive Model and Duty Rating ND/HD on
Defaults by Drive Model and
4.6 Auto-Tuning
4
151