• Remove the correct section of the wiring cover to make wiring easier.
• Do not let strain on the wiring cause damage. Use a strain relief near the wiring to release the tension.
A - Strain relief
Screw
Adapter
Bit
M4
Bit
*1
M5
Bit
M6
Bit
M6
Bit
M8
Bit
M10
*1
When wiring drive models 4089 and smaller, select the correct tools for the wire gauge.
*2
Use 6.35 mm (0.25 in) bit socket holder.
*3
Use a torque wrench that can apply this torque measurement range.
Main Circuit Terminal Block Wiring Procedure
The keypad and front cover must be removed before wiring the main circuit terminal block.
1.
Pull the wiring cover forward to remove it from the drive.
A - Wiring cover
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Figure 3.21 Strain Relief Example
Table 3.3 Recommended Wiring Tools
Bit
Model
Manufacturer
SF-BIT-SL 1,0X4,0-70
PHOENIX CONTACT
SF-BIT-SL 1,2X6,5-70
PHOENIX CONTACT
SF-BIT-HEX 5-50
PHOENIX CONTACT
SF-BIT-SL 1,2X6,5-70
PHOENIX CONTACT
SF-BIT-HEX 6-50
PHOENIX CONTACT
SF-BIT-HEX 8-50
PHOENIX CONTACT
Figure 3.22 Remove the Wiring Cover
3.4 Main Circuit Terminal Block Wiring
Torque Driver Model
(Tightening Torque)
TSD-M 3NM
(1.2 - 3 N∙m)
Wire Gauge
≤ 25 mm
2
(AWG 10):
TSD-M 3NM
(1.2 - 3 N∙m)
Wire Gauge
≥ 30 mm
2
(AWG 8):
-
-
-
-
-
Torque Wrench
-
Wire Gauge
≤ 25 mm
2
(AWG 10):
-
Wire Gauge
≥ 30 mm
2
(AWG 8):
*2 *3
4.1 - 4.5 N∙m
*2 *3
5 - 9 N∙m
*2 *3
3 - 3.5 N∙m
*2 *3
8 - 12 N∙m
*2 *3
12 - 14 N∙m