Omron Q2A Series Technical Manual page 763

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

L4-01 SpAgree Det.Level
No.
Name
(Hex.)
L4-01
SpAgree Det.Level
(0499)
Sets the level to detect speed agree or motor speed when H2-01 to H2-03 = F, 10, 13, 14 [DO Function Select =
SpeedAgree1, USpeedAgree1, FreqDetect 1, FreqDetect 2].
L4-02 SpAgree Det.Width
No.
Name
(Hex.)
L4-02
SpAgree Det.Width
(049A)
Sets the width to detect speed agree or motor speed when H2-01 to H2-03 = F, 10, 13, 14 [DO Function Select =
SpeedAgree1, USpeedAgree1, FreqDetect 1, FreqDetect 2].
L4-03 SpAgree Det.Level(+/-)
No.
Name
(Hex.)
L4-03
SpAgree Det.Level(+/-)
(049B)
Sets the level to detect speed agree or motor speed when H2-01 to H2-03 = 11, 12, 15, 16 [DO Function Select =
SpeedAgree2, USpeedAgree2, FreqDetect 3, FreqDetect 4].
L4-04 SpAgree Det.Width(+/-)
No.
Name
(Hex.)
L4-04
SpAgree Det.Width(+/-)
(049C)
Sets the width to detect speed agree or motor speed when H2-01 to H2-03 = 11, 12, 15, 16 [DO Function Select =
SpeedAgree2, USpeedAgree2, FreqDetect 3, FreqDetect 4].
L4-05 FrefLoss Det.Selection
No.
Name
(Hex.)
L4-05
FrefLoss Det.Selection
(049D)
Enables the detection of a loss of an analog frequency reference when the frequency reference is input from the
MFAI terminals (AI1, AI2, and AI3). Set H2-01 to H2-03 = 4B [DO Function Select = FreqRef Loss] to enable
this function.
If the frequency reference is less than 10% in 400 ms, the drive detects frequency reference loss.
1 : Stop
The drive follows the frequency reference and stops the motor.
2 : Run@L4-06PrevRef
The drive continues to operate at the frequency reference value set in L4-06 [Freq.Ref@RefLoss]. When you
return the external frequency reference value, the drive continues to operate with the frequency reference.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to detect speed agree or motor speed.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width to detect speed agree or motor speed.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level to detect speed agree or motor speed.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width to detect speed agree or motor speed.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the operation when the drive detects a loss of frequency reference.
Figure 12.133 Detection of Frequency Reference Loss
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 L: PROTECTION
Default
(Range)
Determined by A1-02
(Determined by A1-02)
Default
(Range)
Determined by A1-02
(Determined by A1-02)
Default
(Range)
Determined by A1-02
(Determined by A1-02)
Default
(Range)
Determined by A1-02
(Determined by A1-02)
Default
(Range)
1
(1, 2)
763
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents