12.11 T: AUTOTUNING
0 : Inertia Tuning
1 : ASR (Speed Regulator)
2 : Dec Rate Tuning
3 : KEB Tuning
Note:
Settings 0 and 1 are available only when A1-02 = 3, 7 [Control Method = CLVector, PM CLVector].
T3-01 Inertia Test Frequency
No.
Name
(Hex.)
T3-01
Inertia Test Frequency
(0760)
If the load inertia is too large and the drive detects a fault after Inertia Tuning, decrease the setting.
T3-02 Inertia Test Amplitude
No.
Name
(Hex.)
T3-02
Inertia Test Amplitude
(0761)
If the load inertia is too large and the drive detects a fault after Inertia Tuning, decrease the setting. If the drive
detects a fault when T3-01 [Inertia Test Frequency] is set to a low value, adjust this parameter.
T3-03 Motor Inertia
No.
Name
(Hex.)
T3-03
Motor Inertia
(0762)
The default setting is for a Yaskawa standard motor as shown in the motor inertia table. Actual values will be
different when you use induction motors or PM motors.
Note:
Capacities smaller than 37 kW are set in units of 0.0001 kgm
T3-04 System ResponseFrequency
No.
Name
(Hex.)
T3-04
System ResponseFrequency
(0763)
If this input value is too high, it can cause oscillation.

T4: SIMPLE VECTOR

Use T4 parameters to input the data necessary for motor parameter Auto-Tuning when A1-02 = 8 [Control
Method = EZ Vector]. These two modes are available:
830
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency of the test signal applied to the motor during Inertia Tuning. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amplitude of the test signal applied to the motor during Inertia Tuning. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the inertia of the motor. This value uses the test signal response to calculate the load inertia.
2
. Capacities 37 kW and larger are set in units of 0.001 kgm
V/f
CL-V/f
OLV
CLV
AOLV
This parameter uses the load inertia value from the Inertia Tuning process to automatically
calculate and set C5-01 [ASR PGain 1].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
3.0 Hz
(0.1 - 20.0 Hz)
Default
(Range)
0.5 rad
(0.1 - 10.0 rad)
Default
(Range)
Determined by o2-04, C6-
01, and E5-01
(0.0001 - 6.0000 kgm
2
)
2
.
Default
(Range)
10.0 Hz
(0.1 - 50.0 Hz)