12.10 o: KEYPAD
o1-51 Trend Plot Time Scale Setting
No.
Name
(Hex.)
o1-51
Trend Plot Time Scale
Setting
(11CB)
RUN
o1-55 AnGauge Area Selection
No.
Name
(Hex.)
o1-55
AnGauge Area Selection
(11EE)
RUN
0 : + - Area (- o1-56 - o1-56 )
1 : + Area (0 - o1-56 )
o1-56 AnGauge Area Setting
No.
Name
(Hex.)
o1-56
AnGauge Area Setting
(11EF)
RUN

o2: KEYPAD OPERATION

o2-01 LO/RE Key Selection of Function
No.
Name
(Hex.)
o2-01
LO/RE Key Selection of
Function
(0505)
0 : Disabled
You cannot use
to switch between LOCAL and REMOTE Modes.
1 : Enabled
You can use
to switch between LOCAL and REMOTE Modes when the drive is stopped. When LOCAL
Mode is selected,
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when setting b1-07 = 2
[LO/RE Run Selection = Accept RUN]. Clear all personnel from rotating machinery and electrical connections prior to switching
control sources. Failure to comply may cause death or serious injury.
WARNING! Sudden Movement Hazard. Fully examine all mechanical and electrical connections before you change o2-01 [LO/
RE Key Selection of Function] or b1-07 [LO/RE Run Selection]. If b1-07 = 2 [Accept RUN] and there is an active Run command
when you switch from LOCAL to REMOTE Mode, the drive can start suddenly. Failure to obey can cause serious injury or
death.
Function Selection
o2-01 = 0 [Disabled]
o2-01 = 1 [Enabled]
810
V/f
CL-V/f
OLV
CLV
Sets the time scale (horizontal axis) to display the trend plot. When you change this setting, the
drive automatically adjusts the data sampling time. This parameter is only available with an LCD
keypad.
V/f
CL-V/f
OLV
CLV
Sets the range used to display the monitor set in o1-24 [Cust.Monitor 1] as an analog gauge. This
parameter is only available with an LCD keypad.
V/f
CL-V/f
OLV
CLV
Sets the value used to display the monitor set in o1-24 [Cust.Monitor 1] as an analog meter. This
parameter is only available with an LCD keypad.
V/f
CL-V/f
OLV
CLV
Sets the function that lets the drive switch between LOCAL and REMOTE Modes using the
button.
on the keypad will come on.
Table 12.58 Function Settings via o2-01 through b1-07
LOCAL/REMOTE Run Selection
b1-07 = 1 [Cycle RUN]
b1-07 = 2 [Accept RUN]
b1-07 = 1 [Cycle RUN]
b1-07 = 2 [Accept RUN]
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Switching from LOCAL Mode to
REMOTE Mode
The drive will not switch modes.
The drive will not start operating although
the Run command is active. When you set
Run command to active again, the drive
will start to run.
When the Run command is active, the
drive will start to run immediately when
the mode switches from LOCAL to
REMOTE.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
5 s
(1 - 3600 s)
Default
(Range)
1
(0, 1)
Default
(Range)
100.0%
(0.0 - 100.0%)
Default
(Range)
1
(0, 1)
Switching from REMOTE Mode to
LOCAL Mode
The drive will not switch modes.
The drive cannot operate because the Run
command is not enabled.
The drive cannot operate because the Run
command is not enabled.