12.8 L: PROTECTION
L2-07 KEB Accel Time
No.
Name
(Hex.)
L2-07
KEB Accel Time
(048B)
Expert
Set this parameter to 0.0 to disable the function. The drive uses the acceleration time in C1-01, C1-03, C1-05, and
C1-07 to accelerate again after KEB operation completes.
L2-08 Frq.Gain@KEB Start
No.
Name
(Hex.)
L2-08
Frq.Gain@KEB Start
(048C)
Expert
Decreases the output frequency in steps to quickly set the motor to a regenerative condition. Use this formula to
calculate the value:
Output frequency reduction = Motor rated slip before KEB operation × (L2-08/100) × 2
L2-09 KEB Min.Frq Level
No.
Name
(Hex.)
L2-09
KEB Min.Frq Level
(048D)
Expert
These conditions set the quantity of decrease:
• Motor rated slip × (L2-09/100)
• The larger value between the value calculated with L2-08 and the value calculated with L2-09
L2-10 Minimum KEB Time
No.
Name
(Hex.)
L2-10
Minimum KEB Time
(048E)
Expert
When you return power while KEB is operating, the drive continues KEB operation until the time set in L2-10 is
expired. When the DC bus voltage is less than the level of L2-05 [UV Detection Lvl (Uv1)] in one of these
conditions, KEB operation continues until the time set in L2-10 is expired:
• L2-01 = 1 and L2-50 = 2 [RideThru@PwrLoss = Enabled] and [RidThruMode@PwrLoss = KEB Mode].
• L2-01 = 1 and L2-50 = 3 [KEB Stop Mode]
• L2-01 = 1 and L2-50 = 4 [KEB Decel to Stop].
• KEB Ride-Thru 1/2 [H1-xx = 40, 41, 42, or 43] is input into the drive.
750
Figure 12.126 Kinetic Energy Backup Decel Time
V/f
CL-V/f
OLV
CLV
AOLV
Sets the acceleration time to return the frequency to the frequency reference before a power loss
after canceling KEB operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the quantity of output frequency reduction used when KEB operation starts as a percentage
of the motor rated slip before starting KEB operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the quantity of output frequency reduction used when KEB operation starts as a percentage
of the motor rated slip.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum length of time to operate the KEB after the drive detects a momentary power
loss.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
0.0 s
(0.0 to 6000.0 s)
Default
(Range)
100%
(0 - 300%)
Default
(Range)
20%
(0 - 100%)
Default
(Range)
50 ms
(0 - 25500 ms)