Omron Q2A Series Technical Manual page 802

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.9 n: SPECIAL
Adjust this parameter in these conditions:
• If there is resonance or hunting when you use the overvoltage suppression function, increase the setting value.
• If motor response is low when you use the overvoltage suppression function, decrease the setting value in 0.05-
unit increments.
n8-69 Spd Obs. P Gain Control
No.
Name
(Hex.)
n8-69
Spd Obs. P Gain Control
(065D)
Expert
n8-72 Spd Obs. Method Selection
No.
Name
(Hex.)
n8-72
Spd Obs. Method Selection
(0655)
Expert
1 : Method 1
2 : Method 2
n8-74 Light Load Iq Level
No.
Name
(Hex.)
n8-74
Light Load Iq Level
(05C3)
Expert
Note:
• If n8-74 > n8-75 [Mid Load Iq Level (Low)], the drive will detect oPE08 [Parameter Selection Error].
• The change is linear between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [Mid Load Id Current].
n8-75 Mid Load Iq Level (Low)
No.
Name
(Hex.)
n8-75
Mid Load Iq Level (Low)
(05C4)
Expert
Note:
• If n8-74 [Light Load Iq Level] > n8-75, the drive will detect oPE08 [Parameter Selection Error].
• The change is linear between n8-74 and n8-75 and the level of the pull-in current from n8-48 to n8-78 [Mid Load Id Current].
n8-77 Hvy Load Iq Level
No.
Name
(Hex.)
n8-77
Hvy Load Iq Level
(05CE)
Expert
Note:
The change is linear between n8-75 [Mid Load Iq Level (Low)] and n8-77 and the level of the pull-in current from n8-78 [Mid Load Id
Current] to n8-49 [Heavy Load Id Current].
n8-78 Mid Load Id Current
No.
Name
(Hex.)
n8-78
Mid Load Id Current
(05F4)
Expert
802
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain that the drive uses for speed estimation. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the speed estimation method. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Set n8-48 [Pull-In Current (for PM Motors)] to the level of the load current (q-axis current) to be
applied.
V/f
CL-V/f
OLV
CLV
AOLV
Set n8-78 [Mid Load Id Current] to the level of the load current (q-axis current) to be applied.
V/f
CL-V/f
OLV
CLV
AOLV
Set n8-49 [Heavy Load Id Current] to the level of the load current (q-axis current) to be applied.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level of the pull-in current for mid-range loads.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
1.00
(0.00 - 20.00)
Default
(Range)
2
(1, 2)
Default
(Range)
30%
(0 - 255%)
Default
(Range)
50%
(0 - 255%)
Default
(Range)
90%
(0 - 255%)
Default
(Range)
0%
(0 - 255%)