Note:
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
H2-26 Compare2 Mon.Selection
No.
Name
(Hex.)
H2-26
Compare2 Mon.Selection
(1546)
Note:
• The configurable monitor changes when the control method changes.
• To use in through mode, set this parameter to 000 or 031. You can set the terminal output level from the PLC through Modbus
communications or the communication option.
• Refer to H2-xx = 3C and 3D [MFDO Function Select = Comparator 1 and Comparator 1] for more information about the comparator
function.
H2-27 Compare2 Low Limit
No.
Name
(Hex.)
H2-27
Compare2 Low Limit
(1547)
Note:
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
H2-28 Compare2 Up Limit
No.
Name
(Hex.)
H2-28
Compare2 Up Limit
(1548)
Note:
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
H2-29 Compare2 Hysteresis
No.
Name
(Hex.)
H2-29
Compare2 Hysteresis
(1549)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2] for more information
about the comparator function.
H2-30 Compare2 On-Delay Time
No.
Name
(Hex.)
H2-30
Compare2 On-Delay Time
(154A)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator 1 and Comparator 2] for more information
about the comparator function.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [MONITOR]. For
example, set x-xx to 102 to monitor U1-02 [CF Error Code].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-26 [Compare2 Mon.Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit detection level for comparator 1 when the full scale analog output for the
monitor selected in H2-26 [Compare2 Mon.Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the hysteresis level for comparator 2 when the full scale analog output for the monitor
selected in H2-26 [Compare2 Mon.Selection] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the on-delay time for comparator 2.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.7 H: TERMINALS
Default
(Range)
103
(000 - 999)
Default
(Range)
0.0%
(0.0 - 300.0%)
Default
(Range)
0.0%
(0.0 - 300.0%)
Default
(Range)
0.0%
(0.0 - 10.0%)
Default
(Range)
0.0 s
(0.0 - 600.0 s)
693