F5: DIGITAL OUTPUT

No.
Name
(Hex.)
F5-01
Term.P1-PC Function
Select
(0399)
F5-02
Term.P2-PC Function
Select
(039A)
F5-03
Term.P3-PC Function
Select
(039B)
F5-04
Term.P4-PC Function
Select
(039C)
F5-05
Term.P5-PC Function
Select
(039D)
F5-06
Term.P6-PC Function
Select
(039E)
F5-07
Term.M1-M2 Function
Select
(039F)
F5-08
Term.M3-M4 Function
Select
(03A0)
F5-09
DO-A3 Output Mode
Selection
(03A1)

F6: COMMUNICATIONS

No.
Name
(Hex.)
F6-01
Comm.Error Selection
(03A2)
F6-02
Comm Ext Flt Detect
(EF0)
(03A3)
F6-03
Comm Ext Flt Select
(EF0)
(03A4)
F6-04
bUS Err Det.Time
(03A5)
F6-06
Trq Ref/Lim Comms
(03A7)
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal P1-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3
Output Mode Selection = 8 CH Sel (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal P2-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3
Output Mode Selection = 8 CH Sel (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal P3-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3
Output Mode Selection = 8 CH Sel (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal P4-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3
Output Mode Selection = 8 CH Sel (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal P5-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3
Output Mode Selection = 8 CH Sel (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal P6-PC on the DO-A3 option. Set F5-09 = 2 [DO-A3
Output Mode Selection = 8 CH Sel (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal 2NO-2CM on the DO-A3 option. Set F5-09 = 2 [DO-A3
Output Mode Selection = 8 CH Sel (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function of terminal 3NO-3CM on the DO-A3 option. Set F5-09 = 2 [DO-A3
Output Mode Selection = 8 CH Sel (F5-01 to F5-08)] to enable this function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output mode of signals from the DO-A3 option.
0 : 8 CH Individual
1 : Bin Code Output
2 : 8 CH Sel (F5-01 to F5-08)
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor or let the motor continue operating when the drive
detects a bUS [Option Communication Error].
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
4 : AL-Run at d1-04
5 : AL-Ramp Stop
V/f
CL-V/f
OLV
CLV
AOLV
Sets when the drive will detect EF0 [Option Card External Fault] is detected.
0 : Always Detected
1 : Detect@RUN Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor or let the motor continue operating when the drive
detects an EF0 [Option Card External Fault].
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
V/f
CL-V/f
OLV
CLV
AOLV
Sets the delay time for the drive to detect bUS [Option Communication Error].
Note:
When you install an option card in the drive, the parameter value changes to 0.0 s.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that enables and disables the torque reference and torque limit
received from the communication option.
0 : Disabled
1 : Enabled
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.7 F: OPTIONS
Default
Ref.
(Range)
5
645
(0 - 1A7)
7
645
(0 - 1A7)
F
645
(0 - 1A7)
13
645
(0 - 1A7)
1
645
(0 - 1A7)
B
645
(0 - 1A7)
0
646
(0 - 1A7)
0
646
(0 - 1A7)
0
646
(0 - 2)
Default
Ref.
(Range)
1
647
(0 - 5)
0
648
(0, 1)
1
648
(0 - 3)
2.0 s
648
(0.0 - 5.0 s)
0
648
(0, 1)
423
11

Hide quick links:

Advertisement

Table of Contents
loading