H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias,
and select output signal levels.
Calibrate Meters Connected to MFAO Terminals AO1 and AO2
You can use H4-02, H4-03, H4-05, and H4-06 [AO1 An.Out Gain, AO1 An.Out Bias, AO2 An.Out Gain, and AO2
An.Out Bias] to calibrate meters connected to terminals AO1 and AO2.
No.
H4-02
AO1 An.Out Gain
H4-03
AO1 An.Out Bias
H4-05
AO2 An.Out Gain
H4-06
AO2 An.Out Bias
H4-07
AO1 Signal Level Select
H4-08
AO2 Signal Level Select
Figure 12.107
shows the gain and bias.
For example, when the parameter value set to analog output is 0, and a 3 V signal is output to terminal AO1, H4-
03 [AO1 An.Out Bias] is set to 30%.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
Use with Q2pack. Refer to the Q2pack online manual for more information.
Name
Figure 12.107 Analog Output Gain/Bias Configuration Example 1
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Setting Range
-999.9 - 999.9%
-999.9 - 999.9%
-999.9 - 999.9%
-999.9 - 999.9%
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
12.7 H: TERMINALS
Default Setting
100.0%
0.0%
50.0%
0.0%
0
0
723