Omron Q2A Series Technical Manual page 678

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.7 H: TERMINALS
Note:
• Refer to "b9: ZERO SERVO" for more information.
• When you use the Zero Servo function, keep the Run command ON. Zero servo stops the motor and if you turn OFF the Run
command, it will not have power.
32: HiSlipBraking
Setting
Function
32
HiSlipBraking
Note:
• When you restart the drive after you use high-slip braking, make sure that the drive fully stops the motor then clear the high-slip
braking input.
• Refer to "n3: HIGHSLIP/OVEREXCITATION BRAKE" for more information.
34: Fast Stop NO
Setting
Function
34
Fast Stop NO
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
• Fully stop the motor
• Cancel the Run command
• Cancel the fast stop command
Note:
• To use the N.C. switch to input the fast stop command, set 35 [Fast Stop NC].
• Refer to
"C1-09 Fast Stop Time on page
NOTICE: Fast deceleration can trigger an overvoltage fault. To prevent and uncontrolled motor and to make sure that the motor
stops quickly and safely, set an applicable Fast Stop time in C1-09 [Fast Stop Time]. When there is a fault, the drive output will
turn off and the motor will coast to stop.
35: Fast Stop NC
Setting
Function
35
Fast Stop NC
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
• Fully stop the motor
• Cancel the Run command
• Cancel the fast stop command
Note:
• To use the N.O. switch to input the fast stop command, set 34 [Fast Stop NO].
• Refer to
"C1-09 Fast Stop Time on page
NOTICE: Fast deceleration can trigger an overvoltage fault. To prevent and uncontrolled motor and to make sure that the motor
stops quickly and safely, set an applicable Fast Stop time in C1-09 [Fast Stop Time]. When there is a fault, the drive output will
turn off and the motor will coast to stop.
Figure 12.79
shows an example of how fast stop operates.
678
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to use high-slip braking to stop the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is ON while
the drive is operating.
567" for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the input terminal is ON while
the drive is operating.
567" for more information.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents