Omron Q2A Series Technical Manual page 624

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.5 E: MOTOR
E5-01 PM Mot Code Selection
No.
Name
(Hex.)
E5-01
PM Mot Code Selection
(0329)
Note:
• If the drive hunts or shows an alarm after you use a motor code, use the keypad to enter the value shown on the nameplate to E5-xx.
• When you use a PM motor other than a Yaskawa SMRA, SSR1, or SST4 series, set E5-01 = FFFF.
Figure 12.69
gives information about the motor code setting digits.
E5-02 PM Mot Rated Power (kW)
No.
Name
(Hex.)
E5-02
PM Mot Rated Power (kW)
(032A)
These types of Auto-Tuning will automatically set this parameter:
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
• PM Rotational Auto-Tuning
E5-03 PM Mot Rated Current (FLA)
No.
Name
(Hex.)
E5-03
PM Mot Rated Current
(FLA)
(032B)
Note:
When the drive model changes, the display units for this parameter also change.
• 0.01 A: 4002 to 4023
• 0.1 A: 4031 to 4675
The drive automatically sets E5-03 to the value input for "PM Motor Rated Current" after you do these types of
Auto-Tuning:
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
• PM StaTun for Stator Resistance
• PM Rotational Auto-Tuning
E5-04 PM Mot Pole Count
No.
Name
(Hex.)
E5-04
PM Mot Pole Count
(032C)
Note:
• When A1-02 = 7 [Control Method = PM CLVector], the maximum value is 120.
• When A1-02 = 5, 6 or 8 [PM OLVector, PM AOLVector or EZ Vector], the maximum value is 48.
624
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to set some
parameters to their correct settings automatically.
Figure 12.69 PM Motor Code
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PM motor rated power.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PM motor rated current (FLA).
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of PM motor poles.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
Determined by A1-02, o2-
04, and C6-01
(0000 - FFFF)
Default
(Range)
Determined by E5-01
(0.10 - 650.00 kW)
Default
(Range)
Determined by E5-01
(10% to 200% of the drive
rated current)
Default
(Range)
Determined by E5-01
(2 - 120)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents