Omron Q2A Series Technical Manual page 652

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.6 F: OPTIONS
Register
No.
Command source update (15E7H)
bit 0
During Run
bit 1
During Reverse Run
bit 2
Drive Ready
bit 3
Fault
bit 4
Frequency Command Setting Fault
bit 5
No response from slave
bit 6
Communication Error
1
bit 7
No response from slave 10 consecutive attempts.
bit 8
Communication fault has occurred 10 consecutive times.
bit 9
Receive broadcast command while drive is running
bit A
Communication error with master drive
bit B -
Reserved
D
bit E
ComRef status
bit F
ComCtrl status
Output frequency or frequency reference (Drive Status Bit 4: ON)
(Drive 1) (15E8)
2
Drive Status Bit 4 = 0 [Output Frequency]
Drive Status Bit 4 = 1 [Frequency Reference]
3
Drive Status (Drive 2) (15E9H)
Output frequency or frequency reference (Drive Status Bit 4: ON)
4
(Drive 2) (15EAH)
5
Drive Status (Drive 3) (15EBH)
Output frequency or frequency reference (Drive Status Bit 4: ON)
6
(Drive 3) (15ECH)
7
Drive Status (Drive 4) (15EDH)
Output frequency or frequency reference (Drive Status Bit 4: ON)
8
(Drive 4) (15EEH)
Slave Address for Reg. Access + During Modbus process & ErrCode
(15EFH)
bit 0
00H: Modbus Communication Complete
bit 1
02H: Register number not registered
bit 2
21H: Upper/Lower Limit Fault
bit 3
22H: Write Mode Error
bit 4
23H: Write performed during occurrence of Uv
bit 5
24H: Write performed while writing parameter settings
9
bit 6
FFH: During Modbus Communication
bit 7
Slave address
0: Modbus command ignored
bit 8
1: Drive 1
bit 9
2: Drive 2
bit A
4: Drive 3
5: Drive 4
11
Register number (15F0H)
12
Data (write register) (15F1H)
F6-20 MLII Address
No.
Name
(Hex.)
F6-20
MLII Address
(036B)
652
Table 12.38 Monitor Data
V/f
CL-V/f
OLV
CLV
AOLV
Sets the station address for MECHATROLINK communication. Restart the drive after changing
this setting.
Description
1: Upper/Lower Limit Fault
1: Response has timed out.
1: A fault has been detected from a slave.
1: Timeout has occurred 10 consecutive times.
1: Fault has occurred from a slave 10 consecutive times.
1: Drive operates in as specified by the broadcast message command.
1: The slave cannot communicate with the master because of a communication error.
The unit of measure changes when o1-03 changes.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
0021h
(MECHATROLINK-II:
0020h - 003Fh,
MECHATROLINK-III:
0003h - 00EFh)