L3-39 CurLim Filt@Accel
No.
Name
(Hex.)
L3-39
CurLim Filt@Accel
(11D3)
Note:
Set L3-01 = 4 [StallP Mode@Accel = ILim Mode] to enable this function.
L3-40 CurLim SCurve@Acc/Dec
No.
Name
(Hex.)
L3-40
CurLim SCurve@Acc/Dec
(11D4)
Makes the best motor acceleration rate for start up. If you set this parameter to 1, it will make acceleration more
stable, but it can also increase the acceleration time to be longer than the set time. If the drive detects oC
[Overcurrent] faults immediately after acceleration starts, set this parameter.
0 : Disabled
1 : Enabled
Note:
Set L3-01 = 4 [StallP Mode@Accel = ILim Mode] to enable this function.
L3-50 StallP@Decel Mode
No.
Name
(Hex.)
L3-50
StallP@Decel Mode
(0458)
Note:
1. To connect a dynamic braking option (braking resistor or braking resistor unit) to the drive, set this parameter to 0 or 3. Parameter
values 1, 2, 4, and 5 will enable Stall Prevention function during deceleration, and the dynamic braking option will not function.
2. The setting range changes when the A1-02 [Control Method] value changes:
• When A1-02 = 5 [PM OLVector], setting range is 0 to 2
• When A1-02 = 6, 7, or 8 [PM AOLVector, PM CLVector, or EZ Vector], setting range is 0, 1.
Stall Prevention during deceleration controls the deceleration as specified by the DC bus voltage and does not let
high inertia or fast deceleration cause ov [Overvoltage] faults.
0 : General Purpose
The drive decelerates as specified by the deceleration time. When the DC bus voltage is more than the Stall
Prevention level, the drive stops deceleration until the DC bus voltage is less than the Stall Prevention Level. The
drive then starts to decelerate at the set deceleration time. Frequent use of Stall Prevention will help prevent ov
faults when the deceleration time is shorter than the drive can usually accept.
Note:
The Decel Stall Prevention function will increase the deceleration time to stop and the deceleration time will be longer than the setting.
This function is not applicable for conveyor applications because the precision of the stop position is very important. As an alternative,
use a dynamic braking option in these applications.
The input voltage setting of E1-01 [Input AC Supply Voltage] sets the DC bus voltage level for Stall Prevention.
Drive Input Voltage
400 V class
Figure 12.132
shows the Stall Prevention during deceleration function.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant to adjust the acceleration rate when L3-01 = 4 [StallP Mode@Accel = ILim
Mode]. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable and disable the best Jerk Control Settings used for current-limited
acceleration.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
Table 12.53 Stall Prevention Level during Deceleration
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Stall Prevention Level during Deceleration
754 V
12.8 L: PROTECTION
Default
(Range)
100.0 ms
(1.0 - 1000.0 ms)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(Determined by A1-02)
761