7.5 Minor Faults/Alarms
Code
Name
MECHATROLINK Watchdog
E5
Timer Err
Note:
• If the drive detects this error, the terminal assigned to H2-01, H2-02, and H2-03 = 4 [2NO-2CM Func Selection, 3NO-3CM Func Selection, and 4NO-4CM Funct Selection =
Alarm] will be ON.
• If the drive detects this error, it will operate the motor as specified by the stop method set in F6-25 [MLII Watchdog Error Sel].
Code
Name
EF
FWD/REV Run Command Input
Error
Note:
• If the drive detects EF, the motor will ramp to stop.
• If the drive detects this error, the terminal assigned to H2-01, H2-02, and H2-03 = 4 [2NO-2CM Func Selection, 3NO-3CM Func Selection, and 4NO-4CM Funct Selection =
Alarm] will be ON.
Code
Name
EF0
Option Card External Fault
Note:
• The drive detects this error if the alarm function on the external device side is operating.
• If the drive detects this error, the terminal assigned to H2-01, H2-02, and H2-03 = 4 [2NO-2CM Func Selection, 3NO-3CM Func Selection, and 4NO-4CM Funct Selection =
Alarm] will be ON.
• Set the stopping method for this fault in F6-03 [Comm Ext Flt Select (EF0)].
Code
Name
EF1
External Fault (Terminal DI1)
Note:
If the drive detects this error, the terminal assigned to H2-01, H2-02, and H2-03 = 4 [2NO-2CM Func Selection, 3NO-3CM Func Selection, and 4NO-4CM Funct Selection =
Alarm] will be ON.
Code
Name
EF2
External Fault (Terminal DI2)
Note:
If the drive detects this error, the terminal assigned to H2-01, H2-02, and H2-03 = 4 [2NO-2CM Func Selection, 3NO-3CM Func Selection, and 4NO-4CM Funct Selection =
Alarm] will be ON.
Code
Name
EF3
External Fault (Terminal DI3)
Note:
If the drive detects this error, the terminal assigned to H2-01, H2-02, and H2-03 = 4 [2NO-2CM Func Selection, 3NO-3CM Func Selection, and 4NO-4CM Funct Selection =
Alarm] will be ON.
Code
Name
EF4
External Fault (Terminal DI4)
276
Causes
The drive detected a watchdog circuit exception
while it received data from the controller.
Causes
A forward command and a reverse command were
input at the same time for longer than 0.5 s.
Causes
The communication option card received an
external fault from the controller.
Programming error occurred on the controller side.
Causes
MFDI terminal DI1 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-01 = 2C to 2F] is set to MFDI
terminal DI1, but the terminal is not in use.
Causes
MFDI terminal DI2 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-02 = 2C to 2F] is set to MFDI
terminal DI2, but the terminal is not in use.
Causes
MFDI terminal DI3 caused an external fault through
an external device.
The wiring is incorrect.
External Fault [H1-03 = 2C to 2F] is set to MFDI
terminal DI3, but the terminal is not in use.
Causes
MFDI terminal DI4 caused an external fault through
an external device.
The wiring is incorrect.
Possible Solutions
Examine the MECHATROLINK cable connection. If this error
occurs frequently, examine the wiring and decrease the effects of
electrical interference as specified by these manuals:
• MECHATROLINK-II Installation Guide (MECHATROLINK
Members Association, manual number MMATDEP011)
• MECHATROLINK-III Installation Manual
(MECHATROLINK Members Association, publication
number MMATDEP018)
Possible Solutions
Examine the forward and reverse command sequence and correct
the problem.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input from the controller.
Examine the operation of the controller program.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI1.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI2.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI3.
Correctly set the MFDI.
Possible Solutions
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input in the MFDI.
Correctly connect the signal line to MFDI terminal DI4.