Omron Q2A Series Technical Manual page 791

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

n4-67 SpEstim Gain SwFrequency
No.
Name
(Hex.)
n4-67
SpEstim Gain SwFrequency
(1B87)
If the output frequency > n4-67, the drive will select n4-63 and n4-65. If the output frequency < n4-67, the drive
will select n4-64 and n4-66.
n4-68 SpEstim Filter Time Constant
No.
Name
(Hex.)
n4-68
SpEstim Filter Time
Constant
(1B88)
If the motor speed oscillates in the high speed range, set the value to 0.010 s.
n4-69 Flux Control Response
No.
Name
(Hex.)
n4-69
Flux Control Response
(1B89)
If step-out occurs when the load changes, decrease the setting value in 1.00 increments.
Note:
If heavy loads decrease motor speed, increase the setting value in 1.00 increments. If it does not get better, increase n4-74 [Flux Control
Limit] in 20% increments.
n4-70 Speed Comp@LowFrequency
No.
Name
(Hex.)
n4-70
Speed
Comp@LowFrequency
(1B8A)
This function makes the control more stable when operating at low speeds. Increase the setting in 0.3 Hz
increments at the time of low-speed references with no load.
Note:
If you increase this parameter to make the speed references for low speeds more stable, it can make the speed control less accurate.
n4-71 Flux Detect Method
No.
Name
(Hex.)
n4-71
Flux Detect Method
(1B8B)
1 : Method 1
Estimates magnetic flux by voltage command.
2 : Method 2
Estimates magnetic flux by voltage detection.
n4-72 Spd Fbk Mode
No.
Name
(Hex.)
n4-72
Spd Fbk Mode
(1B8C)
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the switching frequency for estimation gain for these parameters:
n4-63 [HF SpdEstim Response]
n4-64 [LF SpdEstim Response]
n4-65 [HF FlxEstim Response]
n4-66 [LF FlxEstim Response]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant for the speed estimation value. Usually it is not necessary to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Unifies control of magnetic flux to make motor vibrations more stable.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to make the drive more stable when operating at low speeds. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Chooses the method of estimating the magnetic flux.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the requirement for an encoder option when A1-02 = 4 [Control Method = Adv OLVector].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.9 n: SPECIAL
Default
(Range)
6.00 Hz
(0.00 - E1-04)
Default
(Range)
1 ms
(1 - 10 ms)
Default
(Range)
1.00
(0.00 - 60.00)
Default
(Range)
0.60 Hz
(0.00 - 1.50 Hz)
Default
(Range)
1
(1, 2)
Default
(Range)
12
1
(1, 2)
791