Code
Name
oFb00
Option Not Compatible with Port
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for this fault.
Code
Name
oFb01
Option Fault/Connection Error
Note:
Do a Fault Reset to clear the fault.
Code
Name
oFb02
Duplicate Options
Note:
Do a Fault Reset to clear the fault.
Code
Name
oFb03 to
Option Card Error Occurred at
oFb11
Option Port CN5-B
Note:
Do a Fault Reset to clear the fault.
Code
Name
oFb12 to
Option Card Error Occurred at
oFb17
Option Port CN5-B
Note:
Do a Fault Reset to clear the fault.
Code
Name
oFC00
Option Not Compatible with Port
Note:
• Do a Fault Reset to clear the fault.
• Fault trace is not available for this fault.
Code
Name
oFC01
Option Fault/Connection Error
Note:
Do a Fault Reset to clear the fault.
Code
Name
oFC02
Duplicate Options
Note:
Do a Fault Reset to clear the fault.
Code
Name
oFC03 to
Option Card Error Occurred at
oFC11
Option Port CN5-C
Note:
Do a Fault Reset to clear the fault.
Code
Name
oFC12 to
Option Card Error Occurred at
oFC17
Option Port CN5-C
Note:
Do a Fault Reset to clear the fault.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Causes
The option card connected to connector CN5-B is
not compatible.
Causes
The option card connected to connector CN5-B was
changed during operation.
Causes
The same option cards or the same type of option
cards are connected to connectors CN5-A, B, and C.
Causes
A fault occurred in the option card.
Causes
A fault occurred in the option card.
Causes
The option card connected to connector CN5-C is
not compatible.
Causes
The option card connected to connector CN5-C was
changed during operation.
Causes
The same option cards or the same type of option
cards are connected to connectors CN5-A, B, and C.
Causes
A fault occurred in the option card.
Causes
A fault occurred in the option card.
Possible Solutions
Connect the option card to the correct connector.
Note:
DO-A3, AO-A3, PG-B3, and PG-X3 options can connect to
connector CN5-B. Use connector CN5-C when connecting
only one encoder option card.
Possible Solutions
1.
De-energize the drive.
2.
Refer to the option card manual and correctly connect the
option card to the connector on the drive.
Possible Solutions
Connect the option card to the correct connector.
Possible Solutions
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Possible Solutions
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Possible Solutions
Connect the option card to the correct connector.
Note:
AI-A3, DI-A3, and communication option cards cannot be
connected to the CN5-C connector.
Possible Solutions
1.
De-energize the drive.
2.
Refer to the option card manual and correctly connect the
option card to the connector on the drive.
Possible Solutions
Connect the option card to the correct connector.
Possible Solutions
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.
Possible Solutions
1.
De-energize the drive.
2.
Make sure that the option card is correctly connected to the
connector.
3.
If the problem continues, replace the option card.