Omron Q2A Series Technical Manual page 713

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

Note:
• Refer to H3-xx "MFAI Setting Values" for the analog input setting values.
• When you will not use the terminal, set H3-40 to H3-42 = 0. The through mode function is not supported.
• You cannot use H3-40 to H3-42 to set these MFAI terminals:
H3-xx Setting Value
H3-01 AI1 Signal Level Select
No.
Name
(Hex.)
H3-01
AI1 Signal Level Select
(0410)
0 : 0 to 10V (Lower Limit at 0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
1 : -10 to +10V (Bipolar Reference)
The voltage signal is -10 Vdc to 10 Vdc. This setting enables positive and negative polarity signals. When the
drive uses this setting as the frequency reference, a Forward Run command will run the motor in reverse and a
Reverse Run command will run the motor forward. The gain and bias settings will cause the signal to be a
negative number.
2 : 4 to 20 mA
The current signal is 4 mA to 20 mA. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
3 : 0 to 20 mA
The current signal is 0 mA to 20 mA. The minimum input level limit is 0%. The drive will read a negative input
signal caused by gain and bias settings as 0%.
Note:
When H3-01 = 0, 1, set DIP switch S1-1 to the V side (voltage). When H3-01 = 2, 3, set DIP switch S1-1 to the I side (current). The
default setting is the V side (voltage).
H3-02 AI1 Function Selection
No.
Name
(Hex.)
H3-02
AI1 Function Selection
(0434)
H3-03 AI1 Gain Setting
No.
Name
(Hex.)
H3-03
AI1 Gain Setting
(0411)
RUN
This parameter sets the quantity of reference for the function set for terminal AI1 as a percentage when 10 V (or
20 mA) is input.
Use this parameter and H3-04 [AI1 Bias Setting] to adjust the characteristics of the analog input signal to terminal
AI1.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
1
2
4
5
30
31
32
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input signal level for MFAI terminal AI1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a function for MFAI terminal AI1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal input to MFAI terminal AI1.
Function
AuxFreqRef1
AuxFreqRef2
FrqBIAS Frq
Freq Gain
Q2pack AI1
Q2pack AI2
Q2pack AI3
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.7 H: TERMINALS
Default
(Range)
0
(0 - 3)
Default
(Range)
4
(0 - 32)
Default
(Range)
100.0%
(-999.9 - +999.9%)
713