11.10 N: Special; N1: Hunting Prevention; N2: Afr - Auto Freq Regulation - Omron Q2A Series Technical Manual

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

11.10 n: SPECIAL

n1: HUNTING PREVENTION

No.
Name
(Hex.)
n1-01
HuntPrev Selection
(0580)
n1-02
HuntPrev Gain Setting
(0581)
Expert
n1-03
HuntPrev Time Constant
(0582)
Expert
n1-05
HuntPrev Gain Reverse
Mode
(0530)
Expert
n1-08
CurrDetect Method
(1105)
Expert
n1-13
DCBus Stab.Control
(1B59)
Expert
n1-14
DCBus Stab Time
(1B5A)
Expert
n1-15
PWM VOffset
Calibration
(0BF8)
Expert
n1-16
HuntPrev HiFc Gain
(0BFB)
n1-17
HuntPrev HiFc Filter
(0BFC)
Expert

n2: AFR - AUTO FREQ REGULATION

No.
Name
(Hex.)
n2-01
AFR Gain
(0584)
n2-02
AFR Time 1
(0585)
n2-03
AFR Time 2
(0586)
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to prevent hunting.
0 : Disabled
1 : Enabled
2 : Enabled (High Carrier)
V/f
CL-V/f
OLV
CLV
AOLV
Adjusts the behavior of the hunting prevention function. Usually it is not necessary to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant of the hunting prevention function. Usually it is
not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the performance of the hunting prevention function. This parameter adjusts
Reverse run. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets how the drive decreases the motor vibration that is caused by leakage current.
Usually it is not necessary to change this setting.
1 : 2-Phases
2 : 3-Phases
V/f
CL-V/f
OLV
CLV
AOLV
Sets the oscillation suppression function for the DC bus voltage.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets a length of time for the drive to suppress oscillation in relation to the DC bus
voltage. Set n1-13 = 1 [DCBus Stab.Control = Enabled] to enable this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the calibration method that the drive uses to decrease torque/current ripple.
1 : No Calibration
2 : Calib@Next Start
3 : Calib@Every Start
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for the hunting prevention function. This parameter functions best with a
high carrier frequency. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of the hunting prevention function. Usually it is not necessary to
change this setting.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the AFR function as a magnification value. Usually it is not necessary
to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that sets the rate of change for the AFR function. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that sets the speed difference of the AFR function. Use this
parameter for speed searches or regeneration. Usually it is not necessary to change this
setting.
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM

11.10 n: SPECIAL

Default
Ref.
(Range)
Determined by o2-04
783
(0 - 2)
1.00
783
(0.00 - 2.50)
Determined by o2-04
783
(0 - 500 ms)
0.00
783
(0.00 - 2.50)
1
784
(1, 2)
0
784
(0, 1)
100.0 ms
784
(50.0 - 500.0 ms)
Determined by A1-02
784
(1 - 3)
Determined by o2-04
784
(0.00 - 2.50)
500 ms
785
(0 - 1000 ms)
Default
Ref.
(Range)
1.00
785
(0.00 - 10.00)
50 ms
785
(0 - 2000 ms)
750 ms
785
(0 - 2000 ms)
457
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents