H4-03 AO1 An.Out Bias
No.
Name
(Hex.)
H4-03
AO1 An.Out Bias
(041F)
RUN
The analog signal output from the AO1 terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-07 [AO1 Signal Level Select].
H4-04 AO2 An.Out Select
No.
Name
(Hex.)
H4-04
AO2 An.Out Select
(0420)
Set the x-xx part of the U: MONITORS. For example, set H4-04 to 102 to monitor U1-02 [Output Frequency].
Note:
• The configurable monitor changes when the control method changes.
• To use in through mode, set this parameter to 000 or 031. You can set the terminal AO2 output level from the PLC through Modbus
communications or the communication option.
H4-05 AO2 An.Out Gain
No.
Name
(Hex.)
H4-05
AO2 An.Out Gain
(0421)
RUN
The analog signal output from the AO2 terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-08 [AO2 Signal Level Select].
Examples of possible settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AO2
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AO2 terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
• H4-04 = 103 [AO2 An.Out Select = Output Current]
• H4-05 = 50.0%
• H4-06 = 0.0% [AO2 An.Out Bias = 0.0%]
• H4-08 = 0 [0 to 10 V]
H4-06 AO2 An.Out Bias
No.
Name
(Hex.)
H4-06
AO2 An.Out Bias
(0422)
RUN
The analog signal output from the AO2 terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-08 [AO2 Signal Level Select].
H4-07 AO1 Signal Level Select
No.
Name
(Hex.)
H4-07
AO1 Signal Level Select
(0423)
Note:
Set jumper S5 on the control circuit terminal block accordingly when changing these parameters.
1 : 0 to 10 Vdc
2 : -10 to +10 Vdc
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from MFAO terminal AO1.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitoring number to be output from the MFAO terminal AO2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is sent from MFAO terminal AO2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitor signal that is sent from MFAO terminal AO2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MFAO terminal AO1 output signal level.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.7 H: TERMINALS
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
103
(000 - 999)
Default
(Range)
50.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
1
(1 - 3)
725