12.5 E: MOTOR
E4-02 = f - (n × p) / 120
• f: Motor rated frequency (Hz)
• n: Rated motor speed (min
• p: Number of motor poles
E4-03 M2 No-Load Current
No.
Name
(Hex.)
E4-03
M2 No-Load Current
(0323)
Note:
The default settings and setting ranges are in these units:
• 0.01 A: 4002 to 4023
• 0.1 A: 4031 to 4675
The drive sets this parameter during Rotational Auto-Tuning and Stationary Auto-Tuning. You can also enter the
motor no-load current shown on the motor test report to E4-03 manually. Contact the motor manufacturer to
receive a copy of the motor test report.
Note:
The default setting of the no-load current is for a 4-pole motor recommended by the manufacturer.
E4-04 M2 Pole Count
No.
Name
(Hex.)
E4-04
M2 Pole Count
(0324)
Auto-Tuning automatically sets E4-04 to the value input for [Number of Motor Poles].
E4-05 M2 L-L Resistance
No.
Name
(Hex.)
E4-05
M2 L-L Resistance
(0325)
Note:
This value is the line-to-line resistance for motor 2. Do not use the single-phase resistance to set this parameter.
The drive automatically calculates this value when Auto-Tuning completes successfully. If you cannot do Auto-
Tuning, get the test report from the motor manufacturer. To calculate the motor line-to-line resistance, use the
information shown on the motor nameplate with one of these formulas:
• E-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
• B-type insulation: the resistance value (Ω) shown on the test report at 75 °C × 0.92
• F-type insulation: the resistance value (Ω) shown on the test report at 115 °C × 0.87
E4-06 M2 Leak Inductance
No.
Name
(Hex.)
E4-06
M2 Leak Inductance
(0326)
The drive sets this parameter during Rotational Auto-Tuning and Stationary Auto-Tuning.
Note:
You cannot usually find the quantity of voltage drop on the motor nameplate. If you do not know the value of the motor 2 leakage
inductance, get the test report from the motor manufacturer.
622
-1
(r/min))
V/f
CL-V/f
OLV
CLV
Sets the no-load current for motor 2 in amps when operating at the rated frequency and the no-
load voltage.
V/f
CL-V/f
OLV
CLV
Sets the number of poles for motor 2.
V/f
CL-V/f
OLV
CLV
Sets the line-to-line resistance for the motor 2 stator windings.
V/f
CL-V/f
OLV
CLV
Sets the voltage drop from motor 2 leakage inductance as a percentage of Motor Rated Voltage
when motor 2 operates at the rated frequency and rated current.
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
Determined by o2-04 and
C6-01
(0 to E4-01)
Default
(Range)
4
(2 - 120)
Default
(Range)
Determined by o2-04 and
C6-01
(0.000 - 65.000 Ω)
Default
(Range)
Determined by o2-04, C6-
01
(0.0 - 60.0%)