12.3 C: TUNING
8. Check for oscillation when you run the motor at speeds more than the setting in C5-07.
Note:
• If overshooting occurs when acceleration ends, decrease the value set in C5-01 and increase the value set in C5-02.
• If undershoot occurs at stop, decrease C5-03 and increase C5-04.
Use MFDI Switch for Proportional Gain
Note:
If A1-02 = 1 [Control Method = PG V/f Control], you cannot use this function.
You can use the input terminals set for ASR Gain (C5-03) Select [H1-xx = 45] to switch the proportional gains set
with C5-01 and C5-03. When the configured input terminal is deactivated, the proportional gain set for C5-01 is
selected. When the terminal is activated, the proportional gain set for C5-03 is selected. The proportional gain
changes linearly over the time set in C5-02 [ASR ITime 1]. The signals from this MFDI are more important than
C5-07 [ASR Gain Switch Frequency].
Figure 12.51 Proportional Gain through Multi-function Digital Input Switch
Speed Waveform Monitoring Method
To make small adjustments of ASR parameters, monitor the speed waveforms when you make the adjustments.
Table 12.18
shows example settings of parameters to monitor speed waveforms.
Table 12.18 Example Settings of MFAO Terminals to Monitor Speed Waveforms
No.
H4-01
H4-02
H4-03
H4-04
H4-05
H4-06
H4-07
H4-08
These settings cause this MFAO configuration. The MFAO common is terminal A0V:
• Terminal AO1: Outputs the output frequency after SFS in a -10 to +10 V (-100 to +10) range.
• Terminal AO2: Outputs the motor speed in a -10 to +10 V (-200 to +20) range.
The manufacturer recommends that you monitor the output frequency after SFS and the motor speed for delays in
response and differences in reference values.
Adjust ASR Parameters
Use
Table 12.19
to adjust ASR. The table lists parameters for motor 1, but you can make the same changes to
motor 2 parameters when you run a second motor.
Note:
When adjusting the proportional gain and integral time, adjust the proportional gain first.
578
Name
AO1 An.Out Select
AO1 An.Out Gain
AO1 An.Out Bias
AO2 An.Out Select
AO2 An.Out Gain
AO2 An.Out Bias
AO1 Signal Level Select
AO2 Signal Level Select
Setting Value
116
Lets you use terminal FM to monitor U1-
16 [SFS Output Frequency].
100.0%
0.0%
105
Lets you use the terminal AM to monitor
U1-05 [Motor Speed].
50.0%
0.0%
1
Lets you monitor in a -10 to +10 V range.
1