12.7 H: TERMINALS
H5-09 Mbus CE Detect Time
No.
Name
(Hex.)
H5-09
Mbus CE Detect Time
(0435)
H5-10 Mbus 0025H Unit Sel
No.
Name
(Hex.)
H5-10
Mbus 0025H Unit Sel
(0436)
0 : 0.1 V units
1 : 1 V units
H5-11 Mbus ENTER Command Mode
No.
Name
(Hex.)
H5-11
Mbus ENTER Command
Mode
(043C)
0 : Enter Required
You must use the Enter command to enable changes to parameters. Make all parameter changes then input the
Enter command.
1 : No Enter Required
It is not necessary to input the Enter command to change parameters.
H5-12 Mbus Run Command Method Sel
No.
Name
(Hex.)
H5-12
Mbus Run Command
Method Sel
(043D)
0 : F/ST R/ST
The drive uses bit 0 in command data 0001H of the Modbus register in the motor forward Run command (bit 0 =
1) and the stop command (bit 0 = 0). The drive uses bit 1 in the motor reverse Run command (bit 1 = 1) and the
stop command (bit 1 = 0).
1 : RUN/ST F/R
The drive uses bit 0 in command data 0001H of the Modbus register in the motor Run command (bit 0 = 1) and
the stop command (bit 0 = 0). The drive uses bit 1 in the direction of motor rotation command (Forward run (bit1
= 0) or Reverse run (bit 1 = 1)).
728
Figure 12.109 Drive Transmit Wait Time
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for CE [Modbus Communication Error] issues when communication
stops.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the unit of measure used for the Modbus communications monitor register 0025H (output
voltage reference monitor).
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to make the Enter command necessary to change parameters through Modbus
communications.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the input method for the Run command when b1-02 = 2 [Run Comm. Sel 1 = Modbus] or b1-
16 = 2 [Run Comm. Sel 2 = Modbus].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
2.0 s
(0.0 - 10.0 s)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)