b8-26 PM eSave Pwr SP Setpoint
No.
Name
(Hex.)
b8-26
PM eSave Pwr SP Setpoint
(0B47)
Expert
■
b8-28 OverExc Action Selection
No.
Name
(Hex.)
b8-28
OverExc Action Selection
(0B8B)
Expert
When operation is not stable at low speeds, set this parameter to 1 to enable the function.
0 : Disabled
1 : Enabled
■
b8-29 eSave Priority Mode
No.
Name
(Hex.)
b8-29
eSave Priority Mode
(0B8C)
Enable this parameter when there are small changes in the load. It is possible that the motor cannot respond
correctly to changes in the load.
0 : Priority: Drive Response
1 : Priority: Energy Savings
■
b8-50 Standby Mode Selection
No.
Name
(Hex.)
b8-50
Standby Mode Selection
(0B0D)
0 : Disabled
1 : Enabled
Standby Mode decreases how much power the drive consumes when it is in standby.
Standby Mode waits for the drive to stop, then uses the relay output of an MFDO terminal to shut off the input
side electromagnetic contactor (MC) and then shut off the main circuit power supply.
Note:
These conditions are also necessary for Standby Mode:
• Connect an external 24 V power supply.
• Connect a electromagnetic contactor to the drive input side and connect the MFDO terminal set for H2-xx = C [@Standby]. When the
MFDO terminal is OFF, the electromagnetic contactor must be OFF.
• Frequently starting and stopping the drive and regularly opening and closing the electromagnetic contactor will decrease the service life
of the drive.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets a value to increase torque accuracy.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for excitation operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the priority of drive response between changes to the load or Energy-saving control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Standby Mode function.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.2 b: APPLICATION
Default
(Range)
0.0%
(-10.0 - +10.0%)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
561
12