Omron Q2A Series Technical Manual page 634

Driving quality 400 v class 0.55 kw to 315 kw
Hide thumbs Also See for Q2A Series:
Table of Contents

Advertisement

12.6 F: OPTIONS
0 : CN5-C
One option card receives the speed feedback signals from motor 1 and motor 2.
1 : CN5-B
Two option cards receive the speed feedback signals from motor 1 and motor 2.
F1-31 Enc2 Pulse Count (PPR)
No.
Name
(Hex.)
F1-31
Enc2 Pulse Count (PPR)
(03B0)
F1-32 Enc2 Rotat Selection
No.
Name
(Hex.)
F1-32
Enc2 Rotat Selection
(03B1)
Refer to the option card installation manual for more information about how to set the encoder pulse output
sequence and make sure that it is correct.
0 : A leads in FWD Direction
1 : B leads in FWD Direction
F1-33 Enc2 Gear Teeth1
No.
Name
(Hex.)
F1-33
Enc2 Gear Teeth1
(03B2)
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-33 = 0 or F1-34 = 0, the gear ratio is 1.
F1-34 Enc2 Gear Teeth2
No.
Name
(Hex.)
F1-34
Enc2 Gear Teeth2
(03B3)
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-33 = 0 or F1-34 = 0, the gear ratio is 1.
F1-35 Enc2 Pulse Scaling for Monitor
No.
Name
(Hex.)
F1-35
Enc2 Pulse Scaling for
Monitor
(03BE)
When the setting value is a 3-digit value (xyz), the dividing ratio is (1 + x)/yz.
For example, when F1-35 = 032, the dividing ratio is 1/32.
634
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of output pulses for each motor revolution for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output sequence for the A and B pulses from the encoder for motor 2. This parameter
assumes that the motor is operating in the forward direction.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the motor side for motor 2. This parameter and F1-34 [Enc2
Gear Teeth2] set the gear ratio between the motor and encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth on the load side for motor 2. This parameter and F1-33 [Enc2 Gear
Teeth1] set the gear ratio between the motor and encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the ratio between the pulse input and the pulse output of the encoder as a 3-digit number for
motor 2. The first digit is the numerator and the second and third digits set the denominator.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
1024 ppr
(1 - 60000 ppr)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0 - 1000)
Default
(Range)
0
(0 - 1000)
Default
(Range)
001
(001 - 032, 102 - 132 (1 - 1/
32))

Hide quick links: