OFF : Disabled
7B: Fault Reset
Setting
Function
7B
Fault Reset
If the drive detects a fault, the drive will activate the fault relay output, turn off the output, and the motor will
coast to stop.
If the drive detects a fault for which you can set the stopping method, apply the appropriate Stopping Method.
Then push
(RESET) on the keypad to turn the Run command OFF, or activate the fault reset terminal to reset
the fault.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before trying to reset a fault.
7C: Prg Lock
Setting
Function
7C
Prg Lock
You can continue to view parameter setting values when the terminal is OFF [Parameters Cannot be Edited].
ON : Program Lockout
OFF : Parameter Write Prohibit
7D: Drive OH2
Setting
Function
7D
Drive OH2
7E: Node Setup
Setting
Function
7E
Node Setup
7F: Comms Test
Setting
Function
7F
Comms Test
The Self-Diagnostics function connects the transmission terminal of the control terminal block to the reception
terminal. The function transmits the data that the drive sent to make sure that the drive can communicate correctly.
Note:
Refer to Modbus communications "Self-Diagnostics" for the self-diagnostics procedure.
90 to 97: Q2pack DI1 to 8
Setting
Function
90 to 97
Q2pack DI1 to 8
Note:
You cannot set values 90 to 97 for inverse output.
9F: Q2pack Disable
Setting
Function
9F
Q2pack Disable
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the current fault when the Run command is inactive.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to prevent parameter changes when the terminal is OFF.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal is ON. The alarm does not have an
effect on drive operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from the host
controller.
V/f
CL-V/f
OLV
CLV
AOLV
Set the function for the drive to self-test RS-485 serial communications operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets digital inputs used with Q2pack. Refer to the Q2pack Online Manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the Q2pack program saved in the drive.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
12.7 H: TERMINALS
687