12.8 L: PROTECTION
Note:
• The lower torque limit is enabled when you set the torque limit by the following method.
–Set H3-02, H3-06, or H3-10 = 9, D [AI Function Select = FW Trq Lim, GenerTrqLim].
–Use a communication option to set the torque limits
• You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
• If you set the value too low with large loads, the motor can stall.
L7-02 RV Torque Limit
No.
Name
(Hex.)
L7-02
RV Torque Limit
(04A8)
RUN
Note:
• The lower torque limit is enabled when you set the torque limit by the following method.
–Set H3-02, H3-06, or H3-10 = 9, D [AI Function Select = FW Trq Lim, GenerTrqLim].
–Use a communication option to set the torque limits
• You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
• If you set the value too low with large loads, the motor can stall.
L7-03 FW Reg. TrqLimit
No.
Name
(Hex.)
L7-03
FW Reg. TrqLimit
(04A9)
RUN
Note:
• The lower torque limit is enabled when you set the torque limit by the following method.
–Set H3-02, H3-06, or H3-10 = 9, D [AI Function Select = FW Trq Lim, GenerTrqLim].
–Use a communication option to set the torque limits
• You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
• If you set the value too low with large loads, the motor can stall.
L7-04 RV Reg. TrqLimit
No.
Name
(Hex.)
L7-04
RV Reg. TrqLimit
(04AA)
RUN
Note:
• The lower torque limit is enabled when you set the torque limit by the following method.
–Set H3-02, H3-06, or H3-10 = 9, D [AI Function Select = FW Trq Lim, GenerTrqLim].
–Use a communication option to set the torque limits
• You must think about drive capacity when a large quantity of torque is necessary. If you set the value too high, the drive can detect oC
[Overcurrent].
• If you set the value too low with large loads, the motor can stall.
L7-06 TrqLimit Integral Time
No.
Name
(Hex.)
L7-06
TrqLimit Integral Time
(04AC)
Decrease the setting value to increase torque limit responsiveness when you use torque limits and L7-07 = 1
[TrqLimit@Acc/Decel = P-ctrl@Ac/Dec].
If there is hunting when torque limits are active, increase the setting value.
772
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for reversed motoring as a percentage, where motor rated torque is the
100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for forward regenerative conditions as a percentage of the motor rated
torque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for reversed regenerative conditions as a percentage of the motor rated
torque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the integral time constant for the torque limit function.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Default
(Range)
200%
(0 - 300%)
Default
(Range)
200%
(0 - 300%)
Default
(Range)
200%
(0 - 300%)
Default
(Range)
200 ms
(5 - 10000 ms)