11.8 H: TERMINALS
Setting
Function
63
Down Command
65
Up2 Command
66
Dw2 Command
67
SpeedSearch Fmax
68
SpeedSearch Fref
6A
PID Disable
71
PID I Reset
72
PID I Hold
75
PID SS Cancel
76
PID InLv Select
77
PID SP 1
78
PID SP 2
7A
PID BiDir
7B
Fault Reset
7C
Prg Lock
7D
Drive OH2
7E
Node Setup
434
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to decrease the drive frequency reference using a button. Users must also set Setting 62 [Up
Command].
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to increase the frequency reference bias value to accelerate the motor when the terminal is
activated. Set this function and H1-xx = 66 [Dw2 Command] together.
Note:
When using this function, set the optimal bias limit value with d4-08 and d4-09 [Up/Dw2 Bias Upper Limit
and Up/Dw2 Bias Lower Limit].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to increase the frequency reference bias value to accelerate the motor when the terminal is
activated. Set this function and H1-xx = 65 [Up2 Command] together.
Note:
When using this function, set the optimal bias limit value with d4-08 and d4-09 [Up/Dw2 Bias Upper Limit
and Up/Dw2 Bias Lower Limit].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to start speed search using an external reference although b3-01 = 0 [SpSrch@Start Selection =
Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 67 and 68 are set at the same
time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to start speed search using an external reference although b3-01 = 0 [SpSrch@Start Selection =
Disabled].
Note:
The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 67 and 68 are set at the same
time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to disable PID control when b5-01 = 1 [PID Enable = Enabled].
ON : PID control disabled
OFF : PID control enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset and hold the PID control integral to 0 when the terminal is ON.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to hold the integral value of the PID control while the terminal is activated.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PID soft starter function.
ON : Disabled
OFF : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to turn the terminal ON and OFF to switch the PID input level (polarity).
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and H1-xx = 78 [PID SP 2] together. Sets the function to switch the PID setpoint to b5-58 to b5-
60 [PID Setpoint 2 to PID Setpoint 4].
V/f
CL-V/f
OLV
CLV
AOLV
Set this function and H1-xx = 77 [PID SP 1] together. Sets the function to switch the PID setpoint to b5-58 to b5-
60 [PID Setpoint 2 to PID Setpoint 4].
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the PID Bi-Directional function.
ON : Enabled
OFF : Disabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the current fault when the Run command is inactive.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command
before trying to reset a fault.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to prevent parameter changes when the terminal is OFF.
ON : Program Lockout
OFF : Parameter Write Prohibit
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive to display an oH2 [Drive Overheat Warning] alarm when the input terminal is ON. The alarm does
not have an effect on drive operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function in CANopen communications to start the Node Setup function to set the drive node address from
the host controller.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Ref.
683
684
685
685
685
685
686
686
686
686
686
686
686
687
687
687
687