7.6 Parameter Setting Errors
Code
Name
oPE16
Energy Saving Constants Error
Code
Name
oPE18
Online Tuning Param Setting Err
Code
Name
oPE20
PG-F3 Setting Error
Code
Name
oPE33
Digital Output Selection Error
288
Causes
The Energy Saving parameters are not set in the
applicable setting range.
Causes
The parameters that control online tuning are set
incorrectly. In OLV control, one of these parameters
was set when n6-01 = 2 [Online Tune Selection =
VoltageAdjustment]:
• E2-02 [Mot Rated Slip] is set to 30% of the
default setting or lower.
• E2-06 [Motor Leak Inductance] is set to 50% of
the default setting or lower.
• E2-03 = 0 [Mot No-Load Current = 0 A] has
been set.
Causes
The value set in F1-01 [Enc1 Pulse Count (PPR)]
does not agree with the number of encoder pulses.
The calculation encoder signal frequency at
maximum speed is more than 20 kHz.
Causes
These two parameters are set at the same time:
• H2-60 ≠ 0 [2NO-2CM 2nd Function ≠ Through
Mode]
• H2-01 = 1xx [2NO-2CM Func Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-63 ≠ 0 [3NO-3CM 2nd Function ≠ Through
Mode]
• H2-02 = 1xx [3NO-3CM Func Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-66 ≠ 0 [4NO-4CM 2nd Function ≠ Through
Mode]
• H2-03 = 1xx [4NO-4CM Funct Selection =
Inverse output of xx]
These parameter pairs are set incorrectly:
• H2-21 > H2-22 [Compare1 Low Limit >
Compare1 Up Limit]
• H2-27 > H2-28 [Compare2 Low Limit >
Compare2 Up Limit]
Possible Solutions
Make sure that E5-xx is set correctly as specified by the motor
nameplate data.
Possible Solutions
Set E2-02, E2-03, and E2-06 correctly.
Possible Solutions
• Examine the F1-01 value and the number of encoder pulses.
• Set F1-01 correctly.
Decrease the value set for E1-04 [Max Output Frequency] and
make sure that the output frequency of the encoder is not more
than 20 kHz.
Possible Solutions
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
It is not possible to set H2-01 to H2-03 = 1xx [Inverse output
of xx] when using output functions for logic operations (H2-
60, H2-63, H2-66 ≠ 0).
• Set parameters H2-21 ≤ H2-22.
• Set parameters H2-27 ≤ H2-28.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual