12.7 H: TERMINALS
■
14: StallPLev@Rn
Setting Value
Function
14
StallPLev@Rn
Note:
The correct stall prevention level during run is the lower value between:
• The analog input value for the MFAI terminal, or
• The value of L3-06 [StallP Level@Run].
Figure 12.106 Stall Prevention Level during Run through Analog Input
■
15: OutFLowLimSel
Setting
Function
15
OutFLowLimSel
■
16: Mot PTC Input
Setting
Function
16
Mot PTC Input
• You can use the Positive Temperature Coefficient (PLC) thermistor as an auxiliary or alternative detection
function for oL1 [Motor Overload] problems to help prevent heat damage to motors. If the PTC input signal is
more than the overload alarm level, oH3 [Motor Overheating Alarm] will flash on the keypad.
• When the drive detects oH3, the motor stops with the setting in L1-03. When the drive detects oH4, the motor
stops with the setting in L1-04. When the drive incorrectly detects motor overheating problems, set L1-05.
■
30: Q2pack AI1
Setting
Function
30
Q2pack AI1
■
31: Q2pack AI2
Setting
Function
31
Q2pack AI1
722
Figure 12.105 DC Injection Braking Current through Analog Input
V/f
CL-V/f
OLV
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
V/f
CL-V/f
OLV
Enters a signal to adjust the output frequency lower limit level if E1-04 [Max Output Frequency] = 100%.
V/f
CL-V/f
OLV
Uses the motor Positive Temperature Coefficient (PTC) thermistor to prevent heat damage to the motor if the current value
when the 10 V (or 20 mA) analog signal is input is 100%.
V/f
CL-V/f
OLV
Use with Q2pack. Refer to the Q2pack online manual for more information.
V/f
CL-V/f
OLV
Use with Q2pack. Refer to the Q2pack online manual for more information.
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual