The overload tolerance characteristics of the motor change the trigger point for the electronic thermal protector.
This provides motor overheat protection from low speed to high speed across the full speed range.
Load Tolerance
3 : CT 100:1 SpeedRange
Use this setting for drive-dedicated motors with a speed range for constant torque of 1:10.
The speed control for this motor is 10% to 100% when at 100% load. Operating slower than 10% speed at 100%
load will cause motor overload.
Load Tolerance
4 : PM VTorque
Use this setting for vector motors with a speed range for constant torque of 1:100.
The speed control for this motor is 1% to 100% when at 100% load. Operating slower than 1% speed at 100%
load will cause motor overload.
Load Tolerance
5 : PM CTorque
Use this setting for PM motors with derated torque characteristics.
The overload tolerance decreases as motor speed decreases because the cooling fan speed decreases and the ability
of the motor to cool decreases in the low speed range.
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Cooling Capability
This motor is designed to operate with commercial line
power. Operate at a 60 Hz base frequency to maximize
the motor cooling ability.
Cooling Capability
This motor is designed to withstand increased
temperatures during continuous operation in the low
speed range (10% base frequency).
Cooling Capability
This motor is designed to withstand increased
temperatures during continuous operation in the low
speed range (1% base frequency).
5.3 UL Standards
Overload Characteristics
(at 100% motor load)
If the motor operates at frequencies less than 60 Hz, the
drive will detect oL1. The drive triggers a fault relay
output and the motor coasts to stop.
Overload Characteristics
(at 100% motor load)
The motor operates continuously at 10% to 100% base
frequency. Operating slower than 10% speed at 100%
load will cause motor overload.
Overload Characteristics
(at 100% motor load)
The motor operates continuously at 1% to 100% base
frequency. Operating slower than 1% speed at 100% load
will cause motor overload.